CVCS Flashcards

1
Q

What are the power supplies to the Charging Pumps?

A

A pump: PGA-L31
B pump: PGB-L32
E pump: either PGA-L35 or PGB-L36 (Swap breaker and transfer local disconnect switch)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is the mnemonic for actuations of CHB-UV-515, CHA-UV-516, CHB-UV-523?

A

Si-Hi Si-Ci Ci-Hi

CHB-UV-515 SIAS or Hi Temp on the outlet Regen HX 413

CHA-UV-516 SIAS or CIAS

CHB-UV-523 SIAS or Hi Temp on Letdown HX Outlet 135

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Explain a loss of control air on the Letdown Backpressure Controller CHN-PIC-201

A

Valves go closed, letdown diverted to the EDT

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Where can you operate VCT Outlet Valve (UV-501)?

A

B03 in Control Room or locally at NHN-M72

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

If VCT level transmitter LT-227 fails High, how will the plant respond?

A

LT-226 will control between 34% and 44% in VCT

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

If VCT level transmitter LT-226 fails Low, how will the plant respond?

A

LT-227 will control between 58% and 60%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What temperature will cause the RCP Seal Injection Isolation valve (CHN-UV-231P) to isolate?

A

150f

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Fill in the chart for Anti-pumped Charging pumps
LOP LOOP LOPw/SIAS LOOPw/SIAS
Always
Normal
Standby

A

LOP LOOP LOPw/SIAS LOOPw/SIAS
Always Anti Anti
Normal Anti
Standby

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What is the normal status of CHN-UV-532 RWT to BAMP isolation valve?
Why?

A

hand-jacked Open with air removed
to prevent an inadvertent isolation of boration flow paths

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What are the auto-actions of CHN-UV-567 Gas Stripper Outlet Valve?

A

on LT-227 goes above 60%, will shift to direct letdown flow to the Holdup Tank

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What gives you the BLUE light for the RMWP’s?

A

Reactor Makeup Water Tank Lo-Lo
loss of control power
Lo Discharge Pressure

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

How does CHN-PDV-240 fail on:
loss of power
loss of air

A

Fails closed on:
* Loss of Air
* Loss of Power (Non-class DC power)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Why is only one Letdown Control valve in service during normal operations?

A

During normal operation, only one LD Control Valve (110P/110Q) is selected for operation, as
sufficient differential pressure between normal RCS operating pressure and the pressures in the
CVCS system to drive letdown flow at the needed flowrate.** Having only one Letdown Control
Valve aligned for operation ensures that the relief capacity of CHN-PSV-345, the Letdown
Intermediate Pressure Relief valve, is not exceeded.**

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What happens if the “Reactor Make-up Flow Alarm Arming Switch” (CHN-HS-37) is placed in the “NORM OEPR” position while refueling?

A

Makeup water flow will NOT cause an alarm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Is the reactor makeup water flow normally armed during Normal or Refueling ops?

A

Refueling Ops

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What single failure will cause auto makeup to the VCT to stop?

A

CHN-FIC-210X fails to 100%
or
CHN-FIC-210Y fails to 100%
(not LT-227 failure)

17
Q

What level in the Refueling Water Tank (RWT) will trip the BAMP’s?

A

73%

18
Q

What temperature, as sensed by CHN-TI-224, will cause CHE-UV-520 Letdown IX Bypass valve to bypass the IX? Automatic or Manually reset?

A

135 degrees F
must be manually re-aligned