What will block a CW pump start? How is this bypassed?

A

The associated loop condenser outlet valve closed will block CW pump start in that loop.

Can bypass with pushbutton on B07.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

How will UV-11 respond to a loss of all running CW pumps in a loop?

A

UV-11 will auto close when there are no running pumps in a CW loop.

If taken to open then UV-11 will open regardless.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What are the starting interlocks associated with the CW pump discharge valves?

A

CW pump discharge valves:
* 1st pump start IN A LOOP Pump starts and its associated pump discharge goes to 44% open
* 2nd pump start IN A LOOP pump starts and disch valve** goes to 44%. waits for 3 min** and then goes to 100%, after 2nd pump discharge goes 100% then the 1st pump valve goes to 100%
* 1st pump stopped IN A LOOP (with 2 pumps running) Pump switch to stop, associated discharge valve goes to 8% open, the associated pump will trip, and discharge valve full closes. Discharge valve is interlocked closed for 2 min
* Discharge valve of the 2nd pump auto closes to 44% if the cross-tie valve is full open AND only 1 CW Pump is running in the other loop or cross-tie is not FULL open.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is the interlock to open the CW Condenser outlet valves (CWN-HV-9/10)?

A

Pressure switches must indicate that the waterboxes are full.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What cools the CW pump bearing and motor lube oil coolers?

A

(TC) Turbine Cooling Water

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What happens to the HI vibration trip of the CW tower fans on fan start?

A

It is bypassed for 30 seconds.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

State what happens when the first CW pump in a loop is stopped.

What does this prevent?

A

On pump stop:

that pump disch valve starts to close.
At 8% open, the associated pump trips and the valve finishes closing.
This disch valve is interlocked closed for 2 min.
Following pump stop, the running pump discharge valve in the SAME loop will auto close to 44% if:
The cross tie valve is not full open OR
The cross tie valve is full open AND only 1 pump is running in the other loop.
Prevents runout of the running CW pump in the loop

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Where can you emergency stop a Circulating Water Pump?

A

Control Room and locally at the pump breaker