TB 174 - Fire Department Hose Testing Procedures Flashcards
NFPA ____ Standard for Care, Use, Inspection and Service Testing of Hose and Couplings.
1962
Station ___________ shall ensure that all rubber lined, single-jacketed hose, double- jacketed hose, by-pass hose, soft suction hose and synthetic nitrile “all rubber” hose (2” high-rise, pigtails and3”Ladder Pipe) be tested _______ using fire apparatus pumps.
Commander Annually
All _____ suction hose and 2-1/2” ______ pressure high-rise hose shall be tested
annually during Annual Pump Test by the Test Pit Engineer.
Hard High
(LAFD recommends
testing be completed within ___ hours of delivery.)
24
Hose stored for longer than one ____ shall be tested before it is placed back into
service.
Year
Firefighting hand lines
(1”, 1-1/2”, 1-3/4”, 2-1/2”) shall be changed within ___ _______ when damp or dirty.
24 hours
Hose shall be kept out of direct ________.
Sunlight
Station Commanders who identify hose that is in need of replacement due to excessive wear or the ____ year service life has been reached, shall contact the Equipment Engineering Unit at the Supply and Maintenance(S&M) Division for assistance.
Ten
All hose shall be cleaned after ______ use.
Each
Dirty hose shall be washed with clear, cold water. Heavily soiled hose may be washed using a ___ to ____ solution of concentrated liquid soap.
5% 10%
If the hose leaks or the hose jacket fails inspection, identify the damaged area(s) by wrapping the hose with _____ tape at the location(s) where repairs are needed.
Black
All lengths of hose of the same size shall be tested at the ______ service test pressure.
Same
The total length of any hose line being tested shall not exceed _____ feet.
300
Double-jacketed rubber lined hose: By-passes and Soft Suctions shall be tested at
_____ PSI.
300
Single-jacketed synthetic nitrile rubber lined hose: 2” high-rise, 2-1/2” high-rise
Pigtails and 3” Ladder Pipe shall be tested at ____ PSI.
300
Single-jacketed synthetic nitrile rubber lined hose: 4” supply shall be tested at
____ PSI.
250
Double-jacketed rubber lined hose: 1”, 1-1/2”, 1-3/4”and2-1/2” shall be tested at ___ PSI.
400
Single-jacketed thermal plastic lined: (brush hose) shall be tested at ____ PSI.
300
Duration of test: _____ minutes at the required pressure.
Five
Length of line: ____ feet maximum per outlet.
300
Each hose shall be _______ (e.g. pen or marker) around its full circumference at the end
of the hose at the back of each coupling.
Marked
Attach hose to the off-side of the apparatus. The hose shall not be attached to any discharge outlet at, or adjacent to, the pump ________ position (panel side)
Operator
Members shall never stand directly within ___’ in front of the free end of the hose, closer than ___’ on either side of the hose, or straddle a hose in the test area.
15 15
If, during the test, a section of hose is leaking or a section bursts, the service test shall be __________ immediately.
Terminated