Ch 27 Building Codes Flashcards
2 types of fireplaces used in residential construction
prefactricated or factory built
Accessible Mirrors
Must be mounted with the edge of the reflective surface no higher than 40” AFF
Accessible Shower - # of Grab Bars
Must be mounted horizontally on (3) sides
Accessible Shower - Size
30” x 60” Minimum
Accessible Toe Kick
6” D Maximum x 9” H Minimum
Accessible Toilet Floor Space
Require an unobstructed 60” turning circle
Accessible Upper Cabinets and Shelves
Must not exceed 44” AFF when above a work surface
Accessible Urinals
Must have an elongated rim at a maximum height of 17” AFF
Accessory Storage Area
300 sq. ft. per occupant gross
Assembly Occupancy Partitions (750 Sq. Ft. +)
Must be 1-Hour fire rated.
Business Area
100 sq. ft. per occupant gross
Changes of Travel Direction
Require a minimum 60” turning radius
Clear Floor Space - Bathrooms
Must be 30” x 48” at all accessible lavatories, urinals, showers, and bathtubs
Clearance Around Accessible Toilets
Must be 60” along rear wall and 56” along side wall
Clearance in Front of Power Panels
36” D
Commercial Kitchens
200 sq. ft. per occupant gross
Common Path of Egress Travel
Portion of exit access that must be traversed before 2 separate paths of travel to 2 exits are available. This distance must be included in the permitted travel distance.
Common Path of Egress Travel Distance
Must not exceed 100’
Concentrated Assembly Without Fixed Seats (Chairs - Not Fixed)
7 sq. ft. per occupant net
Core Drills
Must not be within 18” of any structural element
Demising Partitions
Must be 1-Hour fire rated between tenant spaces.
Distance for Exit Access Doorways - Non-Sprinklered Building
Equal to or greater than 1/2 the length of the maximum overall diagonal dimension, measured in a straight line between the exit doors or exit access doorways
Distance for Exit Access Doorways - Sprinklered Building
Equal to or greater than 1/3 the length of the maximum overall diagonal dimension, measured in a straight line between the exit doors or exit access doorways
Distance to Fire Extinguisher
Must be located no more than 75’ from the furthest occupant
Door Assemblies in 1-Hour Fire Rated Partitions
Must have a minimum fire protection rating of 20 minutes and be self-closing.
Door Swings In Path of Egress Travel
Must not project more than 7” into required width of path of egress when coming from an occupied space
Education - Classroom
20 sq. ft. per occupant net
Education - Workshops and Vocational Rooms
50 sq. ft. per occupant net
Electrical Receptacles - GFI are required within ___ of a water source
36”
Electrical Receptacles - Height
Must be 18” AFF
Emergency Illumination Duration
Shall be provided for 1.5 hours in the event of a failure of normal lighting
Emergency Illumination Location
Shall be arranged to provide initial illumination along the path of egress
Exercise Room
50 sq. ft. per occupant gross
Exit Access Door - Swing
Must open in the direction of exit travel
Exit Signs - Directional
Should be placed in every location where the direction of travel to reach the nearest exit is not apparent
Exposed Hot Water Pipes and Draings
Must be insulated or protected to reduce risk of burns
Fire Extinguisher Required Calculation
1 fire extinguisher for every 3000 sq. ft
Fireplace dimensions: What is the maximum dimension of the trim piece under the mantle from the face of the fireplace
1 1/2”
Fireplace dimensions: What is the minimum distace from the face of the fireplace to the outer edge of the hearth with a fireplace opening of less that 6 sq ft
16”
Fireplace dimensions: What is the minimum distace from the face of the fireplace to the outer edge of the hearth with a fireplace opening of qreater than or equal to 6 sq ft
20”
Fireplace dimensions: What is the minimum distance from the fireplace opening to the trim under the mantle
12”
Fireplace hearth extensions must be made of either ________ or __________ and be supported by noncombusible material
concrete or masonry
Fireplace hearth must be a minimum of ____ thick
2”
Fireplace trim - at what distance from the fireplace opening can non-combustible trim extend an unlimited distance from the face of the fireplace
At 12” or beyond
Fireplace trim - between 6” - 12” how far can non-combustible trim extend beyond the face of the fireplace
1/8” for every inch from the face (at 6” the trim could extend 6/8” or 3/4”)
Fireplace trim - combustible materials are not allowed within _____ of the fireplace opening
6”
Forward Reach - Wall Mounted Controls
Must be located between 15” - 44” AFF
Glazing in Fire Rated Partitions, Doors, or Sidelights may not exceed _________
240 sq. in.
Grab Bars - Behind Toilets
Must be 36” L
Grab Bars - Mounting Height
33” - 36” AFF
Grab Bars - Side of Toilets
Must be 42” L
Gross Area Calculations
Include stairs, corridors, toilet rooms, mechanical rooms, closets, and interior partition thicknesses
Height of Accessible Countertop
Must not exceed 34” AFF
How to Measure Travel Distance
Taken along the centerline of the natural path of travel starting from the most remote point to the centerline of the exit
Length of Dead End Corridors
Must not exceed 20’ L
Locks Along Path of Egress Travel
Must not require the use of a key, special knowledge, or effort from the egress side
Means of Egress Ceiling Height
Must be no less that 7’6”
Means of Egress Protruding Objects - Depth
All objects located on a wall between 27” - 80” AFF must not protrude more than 4” into an egress path of travel.
Means of Egress Protruding Objects - Height
Must allow 6’8” of clear headroom along the path of egress, including corridors, aisles, and passageways
Means of Egress Protruding Objects - Width
Must not reduce the minimum clean width of accessible routes
Mechanical Equipment Room
300 sq. ft. per occupant gross
Mercantile - Areas on Other Floors
60 sq. ft. per occupant gross
Mercantile - Basement and Grade Floor Areas
30 sq. ft. per occupant gross
Mercantile - Storage, Stock, and Shipping Areas
300 sq. ft. per occupant gross
Minimum Door Height
Must not be less than 7’
Minimum Door Openings
Must be a minimum of 36” W
Minimum Interior Corridor Width
44” Minimum
Mounting Height of Audio/Visual Fire Signal Devices
Between 6’8” - 7’6”
Net Area Calculations
Include just the space actually used
Occupancy Load Greater than 29 - S (Storage)
(2) Exit access doorways must be provided
Occupancy Load Greater than 49 - A (Assembly), B (Business), M (Mercantile)
(2) Exit access doorways must be provided
Pair of Door - Minimum Widths
At least one door must be a minimum of 36” W
Path of Egress Travel cannot pass thru:
Secondary spaces subject to closure by doors or containing storage materials or items that project into the path of travel
Public Corridor Partitions
Must be 1-Hour fire rated.
Pull Side of Door Clear Space
18”
Push Side of Door Clear Space
12”
Required Clear Knee Space
27” H x 30” W x 17” D
Required Locations for Audio/Visual Fire Signal Devices
Every restroom, hallway, lobby, and general assembly area.
Residential SF per occupant:
200 sq. ft. per occupant gross
Service Counters - Accessibility
When over 8’L must have an accessible height service counter of 36” L minimum
Side Reach - Wall Mounted Controls
Must be located between 9” - 48” AFF
Smoke and Heat Detector Coverage must include:
all rooms, corridors, and storage areas
Standing Space Assembly Without Fixed Seats
5 sq. ft. per occupant net
Storage Rooms (100 sq. ft. +)
Must be 1-Hour fire rated.
Toilet - Distance to Side Wall from Centerline
16” - 18”
Toilet Seat Height
Must be between 17” - 19” AFF
Travel Distance
Measured from the most remote point within a floor to the entrance of an exit along the natural and unobstructed path of egress travel.
Travel Distance Maximum
Must not exceed 250’ measured along the path of travel
Unconcentrated Assembly Without Fixed Seats (Tables and Chairs)
15 sq. ft. per occupant net
Visibility of Audio/Visual Fire Signal Devices
Must be visible from any location in the room
ANSI / ICC A117.1
Accessible and Usable Building and Facilities
UBC =
Universal Building Code
BOCA =
BOCA National Building Code
SBC =
Standard Building Code
NBC =
National Building Code
NEC =
National Electric Code
NFPA =
National Fire Protection Association
ASTM =
American Society for Testing Materials
ANSI =
American National Standards Institute
Who is responsible for making sure the design meets all applicable codes & regulations?
The designer
IES =
Illuminating Engineering Society
GA =
Gypsum Association
TCA =
Tile Council of America
A well known organization that approves standards written by other organizations
ANSI
NRTL =
Nationally recognized testing organization
OSHA =
Occupational Safety & Health Administration
UL =
Underwriters Laboratory (one of the most well known testing organizations)
When a complete and total product is successfully tested it receives a:
UL Listed Label
When a product is tested for only certain uses it is given a:
UL Classified Label
Fire tests of door assemblies:
UL 10B
Standard specification for gypsum board:
ASTM C1396
One of the most commonly used tests for fire resistance of construction assemblies is
ASTM E119
Standard Test Methods for Fire Test of Building Construction Assemblies:
ASTM E119
There are 2 parts to the ASTM E119 testing. They are:
(1) Heat transfer through the assembly (2) The hose stream test. Overall the test evaluates an assembly’s ability to prevent the passage of fire, heat and hot gases for a given amount of time
What does the hose stream test determine?
How well an assembly stands up to an impact from falling debris and the cooling and eroding effects of water.
Standard Methods for Fire Tests of Door Assemblies
NFPA 252
What does NFPA 252 evaluate:
The ability of a door assembly to resist the passage of flame, heat and gases. It establishes a time-endurance rating for the assembly, and the hose stream test determines if the door will stay in its frame
Standard for Fire Test for Window and Glass Block Assemblies
NFPA 257
Flooring radiant panel test is applied to:
Carpet, resilient floors, and other floor coverings in corridors
NFPA 253 / ASTM E648
Flooring radiant panel test
Methenamine pill test is applied to
carpets and rugs
ASTMT D2859
Methenamine pill test
Steiner Tunnel Test
ASTM E84
Fire ratings of walls, structure, and floor construction assemblies
ASTM E84
Flame spread rating of finishes
Steiner tunnel test
Contribution of wall finish to rie grown in full scale mockup
Room corner test
Room corner test
NFPA 265
Smoke developed from flaming and nonflaming solid materials
Smoke density chamber test
Smoke density chamber test
NFPA 258
Endurance of glazing for 45 minutes to flame and heat transfer
ASTM E163
Cigarette ignition resistance test of furniture components
NFPA 260 (CAL TB 117)
Cigarette ignition resistance test of furniture components tests:
Separate fabric and fillings of upholstered furniture
Cigarette ignition resistance test of furniture composites
NFPA 261 (CAL TB 116)
Cigarette ignition resistance test of furniture composites tests:
Mockup of a seat cushion, including foam, liner and fabric
Full seating test
NFPA 266 (Cal TB 133)
Full seating test what:
An actual sample of a chair testing to an open flame
Vertical ignition test
NFPA 701
Vertical ignition tests what?
Draperies, curtains and other window treatment as well as banners, awnings, and fabric structures
Standard Test Method for Surface Burning Characteristics of Building Materials
ASTM E84
Fire Rating: What are the 3 classsifcations:
I, II & III or A, B C
What is the flame spread rating of Class I (A)
0-25
What is the flame spread rating of Class II (B)
26-75
What is the flame spread rating of Class III (C)
76 - 200
What is the most fire resistance fire rating?
I (A)
Standard Test Method for Specific Optical Density of Smoke Generated by Solid Materials
ASTM E662
What does ASTM E662 measure?
The amount of smoke given off by a flaming or smoldering material or finish.
Smoke density values are given between 0-800 during the Standard Test Method for Specific Optical Density of Smoke Generated by Solid Materials. What is the min. result codes are looking for?
450
ASTM E648, Flooring Radiant Panel Test is testing for:
Flame spread on carpet in a horizontal installation in a corridor or exit-way under the influence of a fully developed fire in an adjacent space
There are 2 material classes defined by the Flooring Radiant Panel Test. What is required in corridors and exit-ways?
Class I
Standard Test Method for Ignition Characteristics of Finished Textile Floor Covering Materials
ASTM D2859
What does the Room Corner Test determine
The contribution of interior wall and ceiling coverings to room fire growth
Standard Methods of Fire Tests for Evaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth
NFPA 286
Standard Methods of Fire Test for Plame Propagation of Textiles and Films
NFPA 701
NFPA 701 test:
Draperies, curtains and other window treatments
What is a fire partition?
A wall assembly with a fire resistance rating of 1 hour
Where are fire partition required?
Walls separating dwelling units (apartments, dormitories, assisted living facilities), Walls separating guest rooms in hotels, walls separating tenant spaces in a covered mall, corridor walls
Fire partitions are not required if:
Type IIB, IIIB and VB building construction with automatic sprinklers
Fire partitions must provide a continuous barrier. This means that:
The partition must extend from the floor to underside of a fire rated ceiling assembly or roof sturcture
Minimum rating for openings in a fire partition is:
3/4 hour except for corridors, which must be 20 minutes.
What is a fire barrier?
A vertical or horizontal assembly that is fire resistance rated and is designed to restrict the spread of fire, confirm fire to limited areas, and / or afford safe passage for protected egress.
Which is more protective - a fire barrier or a fire partition?
Fire Barrier
Where are fire barriers used?
Stairways, to separate different occupancies within the same building, to separate single occupancies into different fire areas, where specified by building code
What is a smoke barrier?
A continuous vertical or horizontal membrane with a minimum fire-resistance rating of 1 hour, designed and constructed to restrict the movement of smoke.
Building Code Analysis
Occupancy Classifications and Loads Construction Types and Building Sizes Means of Egress Fire and Smoke and Resistant Assemblies Fire Protection System Plumbing and Mechanical Requirements ADA Finish and Furniture Selection
Occupancy Classifications and Loads
Determined by the way that the building or space is to be used
Address different hazardous situations or risk factors associated with each type of use
The projected occupant load is the most influential component in determining the occupancy classification.
Is considered to be the number of people that is assumed to safely occupy a space or building.
Interdependent and should be considered at the beginning of a project.
Occupancy Types
Assembly occupancies (A) Business occupancies (B) Educational occupancies (E) Factory or Industrial occupancies Hazardous occupancies (H) Institutional occupancies (I) Mercantile occupancies (M) Residential occupancies (R) Storage occupancies Utility or Miscellaneous occupancies
Occupancy Classification
Type of activity occurring or occupancy
Number of occupants or occupant load
Unusual hazards or risk factors
Types of Rooms and Spaces
Occupiable space Dwelling unit Sleeping unit Guest room or suite Living area or room Habitable room
Determining Occupant Loads
Sets the number of occupants for which you must provide adequate exiting from a space or building.
Determined for each space or building by either using a given load factor, or by establishing a desired number of occupants.
These methods determine the number of people that must be used to be using the corridors, stairs, and exits in the event of a fire.
Based on the relationship between the size and use of the space or building
The code establishes a minimum level of safety by assigning a predetermined amount called the LOAD FACTOR; the amount of area or square feet required for each occupant based on:
1.Occupancy Classification
2.Specific use of the space
Accessory use area is
A space or room that is used in conjunction with the main occupancy, but does not exceed 10% of the floor area of the main occupancy
Incidental use area is:
An area that is incidental to the main occupancy and has the same classification as the nearest main occupancy but, by code, must be separated by a fire barrier
Combustible:
material that will ignite and burn