U2 Seal Oil Flashcards
What are the AC Air Oil Pump auto starts?
- Air Oil supply press < 4.0# higher than H2 press
- Low Dicharge # at 15#
What are the U2 DC Air Oil Pump Seal auto starts?
Has a 5 Sec delay:
- Air Oil supply press < 4.0# higher than H2 press
- Low Dicharge # at 15#
What are the U2 Vacuum Oil Pump trips for U2 Seal oil?
- Trip on Lo Vac Oil Tank Level after 10 sec delay
- Will restart once level is restored
What are the U2 Vacuum Oil Vacuum Pump trips for U2 Seal oil?
- Trips on High Vacuum Oil Tank Level (10 sec delay) i Will restart when level recovers
What are the U2 H2 Oil pump trips for U2 Seal oil?
- Trips on Lo suction level at (10 sec time delay)
- Restarts when level recovers
At what # do we maintain Air Oil at?
- 7# > Machine Gas #
If LRV-608 fails closed, what happens to Air Oil?
- LRV-610 maintains a constant Air Oil # at 75 #
What maintains Level in the H2 Seal Oil System?
- LRV-606/607
If you get a high level in the H2 seal oil system, what happens?
- LRV-603 opens to maintain level from getting backed up into generator
If you lose H2 Seal oil system, what will maintain it and what happens?
- Vacuum Seal oil will supply it and losing H2 Seal oil will reduce H2 purity
If you lose Vacuum Seal oil system, what will maintain it and what happens?
- Air Seal Oil will maintain both H2 and Vacuum Seal oil at Air Oil #
If you lose Air Seal Oil system, what will maintain it and what happens?
- Nothing can maintain it, and you’ll have to trip
At what temp does H2 Seal Oil try to Maintain?
- 110-130°F with an auto bypass around the cooler to maintain this temp
At what pressure is Vacuum Seal Oil maintained?
- 6# > Air Oil (by SV-601/602)
At what pressure is H2 Seal Oil maintained?
- It follows vacuum oil #
On a diaphram failure, which way does LRV-608 fail?
- Fails Closed
If the H2 sensing line fails (sensing line of machine gas pressure), how will LRV-608 react?
- Fails open filling up the Vac-Oil Tank (loss of Air-Oil)
How does LRV-609 the Vacuum Oil Tank Lvl Cntrl Vlv react to a diaphram failure?
- Fails Open
What happens if LRV-603, H2-Oil overflow valve) fails open?
- results in rapid release of H2 gas to H2 detraining siphon
What happens if LRV-603, H2-Oil overflow valve) fails closed?
- result in oil backing
up into the Generator
What happens on a loss of U2 H2 Seal Oil?
- Lowers purity and is then supplied by Vacuum Seal Oil
What happens on a loss of U2 Vacuum Seal Oil?
- H2 Oil # will be maintained by Air-Oil (Follows what it sees on the Vacuum oil header which would be the Air Oil # that has moved over)