What are the Fire Pump Auto Starts?
Electric Fire Pump - 140# for ≥ 2 Sec
East Diesel FW pump - 130# for ≥ 15 secs
West Diesel FW Pump - 120# for ≥ 25 secs
What is the Diesel Fire Pump Trip?
Engine overspeed @ 2112 RPM
For any given fire, what are the most fire pumps you should expect to see running?
2 Pumps max for a Main Transformer Fire
- Electric FW Pump and East Diesel FW Pump
What is the normal power supply to the fire pump house?
Transformer 7 - Norm
Livingston Rd - Alternate
Can you parallel the two supply power sources to the fire pump house?
No, you cannot parallel them due to the two sources being out of phase
Which unit can manually open ZMO-10 and ZMO-20?
Either unit has the ability to open ZMO-10 and ZMO-20
Which unit is required to manually close ZMO-10 and ZMO-20?
Both units are required to close ZMO-10/20 after them being open
What is the TRM limit for gallons in the Fire Water Tanks?
2 Fire Water Tanks with a min of 565,000gal each
What is the TRM for the Diesel FW Pump Fuel oil tanks?
160 gal each for an 8hr operation
Which fans will trip on high temp (400°F) on thermistor string?
AFX
CPR
CIPX
TSC Filtration Unit
At what temp does the pre-alarm for the fans with the charcoal bed come in?
150°F-220°F
Which fans have charcoal filter fire water protection?
AES AFX CPR CIPX CRP TSC Filtration SATFU
ZMO-10/20 will auto open upon receipt of any of the following fire signals from these areas
- Drumming area
- New fuel receiving area
- Any charcoal filter supplied by fire water system
- Push button for Auxiliary building hose reels
Will general aux building elevation area fire detectors open ZMO-10/20?
No they will not open ZMO-10/20. They just send an alarm.
What does the Fire Siren Enable switch do?
It turns the Fire Logic System OFF and allows reset of the alarms after the local Deluge, CO2 or Fire Detection system is reset