What are the Fire Pump Auto Starts?

A

Electric Fire Pump - 140# for ≥ 2 Sec
East Diesel FW pump - 130# for ≥ 15 secs
West Diesel FW Pump - 120# for ≥ 25 secs

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is the Diesel Fire Pump Trip?

A

Engine overspeed @ 2112 RPM

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

For any given fire, what are the most fire pumps you should expect to see running?

A

2 Pumps max for a Main Transformer Fire

- Electric FW Pump and East Diesel FW Pump

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is the normal power supply to the fire pump house?

A

Transformer 7 - Norm

Livingston Rd - Alternate

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Can you parallel the two supply power sources to the fire pump house?

A

No, you cannot parallel them due to the two sources being out of phase

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Which unit can manually open ZMO-10 and ZMO-20?

A

Either unit has the ability to open ZMO-10 and ZMO-20

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Which unit is required to manually close ZMO-10 and ZMO-20?

A

Both units are required to close ZMO-10/20 after them being open

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What is the TRM limit for gallons in the Fire Water Tanks?

A

2 Fire Water Tanks with a min of 565,000gal each

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What is the TRM for the Diesel FW Pump Fuel oil tanks?

A

160 gal each for an 8hr operation

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Which fans will trip on high temp (400°F) on thermistor string?

A

AFX
CPR
CIPX
TSC Filtration Unit

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

At what temp does the pre-alarm for the fans with the charcoal bed come in?

A

150°F-220°F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Which fans have charcoal filter fire water protection?

A
AES
AFX
CPR
CIPX
CRP
TSC Filtration 
SATFU
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

ZMO-10/20 will auto open upon receipt of any of the following fire signals from these areas

A
  • Drumming area
  • New fuel receiving area
  • Any charcoal filter supplied by fire water system
  • Push button for Auxiliary building hose reels
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Will general aux building elevation area fire detectors open ZMO-10/20?

A

No they will not open ZMO-10/20. They just send an alarm.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What does the Fire Siren Enable switch do?

A

It turns the Fire Logic System OFF and allows reset of the alarms after the local Deluge, CO2 or Fire Detection system is reset

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What is the Fire System Logic Reset button is used for?

A

To restore fire system to normal conditions once:

  • Fire signals are cleared
  • Pumps are stopped locally
  • Both Units have to press their own switch at the same time to reset
17
Q

What TRO 8.7.5 require?

A
  • 3 pumps with 2500gpm capability
  • 2 fire water tanks, each with a minimum usable volume of 565,000 gallons
  • Intact system
18
Q

What TRO 8.7.6 A State?

A

One or more Sprinkler Systems inoperable in areas WITH fire detection
WITHIN 1 hr:
- Verify fire detection instrumentation (electric or pneumatic) for the affected area is OPERABLE.
AND
- Verify that Monitoring Program Action Levels have not been exceeded

19
Q

What TRO 8.7.6 B State?

A

One or more Sprinkler Systems inoperable in areas WITHOUT fire detection
WITHIN 1 hr:
- Patrol the affected area with a fire watch.
- Verify that Monitoring Program Action Levels have not been exceeded.

20
Q

What TRO 8.7.6 C State?

A

Required Action and associated Completion Time of Condition A or Condition B is not met
WITHIN 1 hr:
- Establish a continuous fire watch patrol of affected area.

21
Q

What causes the charcoal in the charcoal filters to catch on fire/heat up?

A

It reacts with the iodine its filtering out

22
Q

What area do each of the CO2 Tanks Protect?

A
71/2 Ton - Old Office Building and Generator Degas
17 Ton Areas:
- 4KV Room
- EDG Rooms
- EDG Fuel Oil Pump Room
- Aux Cable Vault
- CRCV
- Switchgear room cable vault
- Quads 1-4
- MT Lube Oil Tank Rooms
- Lube Oil Tank Rooms
- CRD room
- Hose Reels
23
Q

How does the CO2 Master Valve fail on loss of 250V DC?

A

Fails open

24
Q

How does the CO2 Pilot Valve fail on loss of 250V DC?

A

Fails open

25
How does the CO2 Master Valve fail on loss of pilot pressure?
Fails closed
26
With a fire in the U2 CRCV, what automatically actuates for fire protection?
Halon and Fire Water Sprinkler
27
With a fire in the U1 CRCV, what automatically actuates for fire protection?
Halon only
28
What must you manually actuate for a CRCV fire to both units?
CO2
29
Where are the Fire Water pumps shutdown at?
Locally at their control panels
30
What must you do prior to entering the CRCV?
Manually isolate CO2
31
If you manually operate local selector valves, what will that prevent from happening?
Defeats alarms and bypasses all automatic functions until its reset
32
Is Turbine lagging fire protection automatic?
No, fire has to be locally verified and manually actuated from control room
33
When does the 17 ton compressor lock out and how is it reset?
Locks out on a load shed and it has to be reset in control room via reset push button
34
If Halon is actuated at the cylinder manually, will the extended Halon bottles actuate?
No, they will not
35
If a Diesel fire pump won't start on the first try, what happens next?
- it will keep trying to start, and Engine locks out if it doesn't start within 6 cranking cycles. (15-sec ea)
36
What is the purpose of the INDIVIDUAL ISOLATION SWITCH?
Prevents all auto actuations of CO2 to a protected area
37
What happens on a temp Pre-alarm in the charcoal bed?
CR gets an alarm and procedure directs opening of FP Isolation vlv
38
How does the CO2 Selector Valve fail on loss of power?
Fails closed