Fire Protection Flashcards

1
Q

What are the Fire Pump Auto Starts?

A

Electric Fire Pump - 140# for ≥ 2 Sec
East Diesel FW pump - 130# for ≥ 15 secs
West Diesel FW Pump - 120# for ≥ 25 secs

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is the Diesel Fire Pump Trip?

A

Engine overspeed @ 2112 RPM

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

For any given fire, what are the most fire pumps you should expect to see running?

A

2 Pumps max for a Main Transformer Fire

- Electric FW Pump and East Diesel FW Pump

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is the normal power supply to the fire pump house?

A

Transformer 7 - Norm

Livingston Rd - Alternate

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Can you parallel the two supply power sources to the fire pump house?

A

No, you cannot parallel them due to the two sources being out of phase

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Which unit can manually open ZMO-10 and ZMO-20?

A

Either unit has the ability to open ZMO-10 and ZMO-20

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Which unit is required to manually close ZMO-10 and ZMO-20?

A

Both units are required to close ZMO-10/20 after them being open

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What is the TRM limit for gallons in the Fire Water Tanks?

A

2 Fire Water Tanks with a min of 565,000gal each

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What is the TRM for the Diesel FW Pump Fuel oil tanks?

A

160 gal each for an 8hr operation

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Which fans will trip on high temp (400°F) on thermistor string?

A

AFX
CPR
CIPX
TSC Filtration Unit

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

At what temp does the pre-alarm for the fans with the charcoal bed come in?

A

150°F-220°F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Which fans have charcoal filter fire water protection?

A
AES
AFX
CPR
CIPX
CRP
TSC Filtration 
SATFU
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

ZMO-10/20 will auto open upon receipt of any of the following fire signals from these areas

A
  • Drumming area
  • New fuel receiving area
  • Any charcoal filter supplied by fire water system
  • Push button for Auxiliary building hose reels
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Will general aux building elevation area fire detectors open ZMO-10/20?

A

No they will not open ZMO-10/20. They just send an alarm.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What does the Fire Siren Enable switch do?

A

It turns the Fire Logic System OFF and allows reset of the alarms after the local Deluge, CO2 or Fire Detection system is reset

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What is the Fire System Logic Reset button is used for?

A

To restore fire system to normal conditions once:

  • Fire signals are cleared
  • Pumps are stopped locally
  • Both Units have to press their own switch at the same time to reset
17
Q

What TRO 8.7.5 require?

A
  • 3 pumps with 2500gpm capability
  • 2 fire water tanks, each with a minimum usable volume of 565,000 gallons
  • Intact system
18
Q

What TRO 8.7.6 A State?

A

One or more Sprinkler Systems inoperable in areas WITH fire detection
WITHIN 1 hr:
- Verify fire detection instrumentation (electric or pneumatic) for the affected area is OPERABLE.
AND
- Verify that Monitoring Program Action Levels have not been exceeded

19
Q

What TRO 8.7.6 B State?

A

One or more Sprinkler Systems inoperable in areas WITHOUT fire detection
WITHIN 1 hr:
- Patrol the affected area with a fire watch.
- Verify that Monitoring Program Action Levels have not been exceeded.

20
Q

What TRO 8.7.6 C State?

A

Required Action and associated Completion Time of Condition A or Condition B is not met
WITHIN 1 hr:
- Establish a continuous fire watch patrol of affected area.

21
Q

What causes the charcoal in the charcoal filters to catch on fire/heat up?

A

It reacts with the iodine its filtering out

22
Q

What area do each of the CO2 Tanks Protect?

A
71/2 Ton - Old Office Building and Generator Degas
17 Ton Areas:
- 4KV Room
- EDG Rooms
- EDG Fuel Oil Pump Room
- Aux Cable Vault
- CRCV
- Switchgear room cable vault
- Quads 1-4
- MT Lube Oil Tank Rooms
- Lube Oil Tank Rooms
- CRD room
- Hose Reels
23
Q

How does the CO2 Master Valve fail on loss of 250V DC?

A

Fails open

24
Q

How does the CO2 Pilot Valve fail on loss of 250V DC?

A

Fails open

25
Q

How does the CO2 Master Valve fail on loss of pilot pressure?

A

Fails closed

26
Q

With a fire in the U2 CRCV, what automatically actuates for fire protection?

A

Halon and Fire Water Sprinkler

27
Q

With a fire in the U1 CRCV, what automatically actuates for fire protection?

A

Halon only

28
Q

What must you manually actuate for a CRCV fire to both units?

A

CO2

29
Q

Where are the Fire Water pumps shutdown at?

A

Locally at their control panels

30
Q

What must you do prior to entering the CRCV?

A

Manually isolate CO2

31
Q

If you manually operate local selector valves, what will that prevent from happening?

A

Defeats alarms and bypasses all automatic functions until its reset

32
Q

Is Turbine lagging fire protection automatic?

A

No, fire has to be locally verified and manually actuated from control room

33
Q

When does the 17 ton compressor lock out and how is it reset?

A

Locks out on a load shed and it has to be reset in control room via reset push button

34
Q

If Halon is actuated at the cylinder manually, will the extended Halon bottles actuate?

A

No, they will not

35
Q

If a Diesel fire pump won’t start on the first try, what happens next?

A
  • it will keep trying to start, and Engine locks out if it doesn’t start within 6 cranking cycles. (15-sec ea)
36
Q

What is the purpose of the INDIVIDUAL ISOLATION SWITCH?

A

Prevents all auto actuations of CO2 to a protected area

37
Q

What happens on a temp Pre-alarm in the charcoal bed?

A

CR gets an alarm and procedure directs opening of FP Isolation vlv

38
Q

How does the CO2 Selector Valve fail on loss of power?

A

Fails closed