MFP Turbine Ctrls Flashcards
When are the MFPs forced to speed ctrl?
- Both MS Press xmitters Fail
- Both MFP Hdr # xmitters Fail
- MFP DP Setpoint xmitter Fails
- Other MFP Trip when > 60% Power
- MFP Speed > 5220 (5300) rpm when its forced to speed ctrl
What will override MFP Speed Ctrl on U2?
- MFP 1st Stage # Limiter
- Will close down on control valves to prevent excessive 1st stage #. (@ 105# first stage # and 5300 rpm)
When is MFP ΔP enabled?
- MFP Speed > 3500 rpm
What are the Hardwired MFP trips?
- Manual
- IOPS 110% 5740(5830) rpm
- P14 (SG Hi Hi @ 67% 2/3 on 1 SG)
- SI
- Rx Trip
- Thrust Bearing Wear
What are the DCS MFP trips?
- Lube Oil Pressure Low < 4#(13#) for 5 sec
- Condenser Vacuum Low < 20”(15”) Hg
- Overspeed 107% 5585(5670) rpm
- Loss of suction pressure < 180# for 5 sec
When does the Main Steam to the MFP Automatically open for fast action Main Steam Supply to MFPs in U2
- When MFP steam control valves > 65% open, MS supplies open until control valves < 63%
- When MFP trips, MS to running MFP set to 105#
- Minor perturbation
What steam does U1 MFP Turbine use and when?
- Bypass Steam during Start up, shut down
- Reheat Steam for norm ops
- Can use Aux steam as well for start up
What steam does U2 MFP Turbine use and when?
- Bypass Steam during Start up, shut down
- Reheat Steam for norm ops
- Can use Aux steam as well for start up
What feeds the Steam Flow input for the ΔP Control for program ΔP?
- Total Steam Flow selected Channel
- No Load Set point
What transmitters feed the ΔP Control for actual ΔP?
- UPC-102A/B (Bypass Steam header) (Higher of 2)
- FPC-250A/B (6A FW Htr outlet) (Lower of 2)
What happens when a MFP is forced to speed ctrl?
- Remaining MFP shifts to SPEED CONTROL
- SPEED TARGET set to Max (5220/5300) RPM
- RAMP RATE is calculated to bring speed reference to Max in 20 seconds.
- U2: ARV-11/12 setpoint ramped to 105#
What parameter tells the Main Turbine that power is > 60%?
- Actual Load
Unit 1 > 626.4 MW
Unit 2 > 730.2 MW