CTS and H2 Recombiners Flashcards

1
Q

What is the purpose of the CTS system?

A
  • Limits post-accident containment pressure and temperature to less than design values of 12#
  • Removes radioactive elemental iodine from the containment atmosphere in the event of a DBA.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is the purpose of the H2 Recombiner?

A
  • Control the hydrogen generated in the containment after a loss of coolant accident (LOCA)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is the purpose of DIS?

A
  • The DIS eliminates hydrogen in the containment following a LOCA to prevent a detonation by period ignition of h2 mixtures
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What are the ESF systems in the plant?

A
  • Ctmnt Structure
  • ECCS System
  • Ice Condenser
  • CTS
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What are the CTS pump starts?

A
  • Load Shed (W/ Phase B)
  • Phase B
  • Manual
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What are the CTS pump Trips?

A
  • Load Shed
  • Overload/Overcurrent
  • Manual
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What causes a CTS signal?

A
  • 2.8# (2/4)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What are the fission product barriers?

A
  • Fuel Clad
  • RCS
  • Ctmnt building
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What do you declare if you lose one or potential to lose one fission product barrier?

A
  • Unusual event
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What do you declare if you lose two fission product barriers and potential to lose a thrid fission product barrier (Fuel Clad or RCS Barrier)?

A
  • General Emergency
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What do you declare if you lose any TWO of the following:

  1. Loss or Potential Loss of Fuel Clad.
  2. Loss or Potential Loss of RCS.
  3. Loss of Containment Barrier.
A
  • Site Area Emergency
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What happens on a SAT low-low lvl?

A
  • SAT outlet valves close and eductor suction valves should have closed prior to the SAT Low Low lvl alarm but it sends the signal again
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What is the CTS flow to upper ctmnt spray header?

A
  • 2000gpm
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What is the CTS flow to lower ctmnt spray header?

A
  • 1200gpm
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Which CTS header does RHR feed and how much flow?

A
  • Upper ctmnt spray header only, and 2000gpm
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What is the intended pH of the recirc sump due to CTS?

A
  • 7-10 pH

- want 8.5 pH to keep iodine in solution

17
Q

What is added to the SAT to help remove radioactive iodine?

A
  • Sodium Hydroxide
18
Q

What do we use in the SAT to minimize moisture?

A
  • Nitrogen overpressure
19
Q

Can the H2 Recombiners be started in modes 1-4?

A
  • Yes, but you have to declare the EDGs inoperable because it will over load the EDGs in the event of an SI with LOOP
20
Q

What powers the H2 recombiners?

A
  • 11/21 B

- 11/21 C

21
Q

Will the H2 recombiners trip on a load shed?

A
  • No, they do not
22
Q

Will the CTS pump auto start on a Containment Spray Signal?

A
  • No
23
Q

Main Steam Isolation comes from with Ctmnt iso phase?

A
  • Phase B (Auto only)
24
Q

What will 2.8# in ctmnt cause?

A
  • Phase B
  • Ctmnt Spray Actuation
  • Steam Line Iso (auto only)
25
Q

What are the auto actions of a Ctmnt Spray Actuation?

A
  • CTS pump disch valves open
  • SAT outlet valves open
  • CTS pump seq on after approx. a 4 min time delay (as long as white light is lit)
26
Q

What are the H2 production sources?

A
  • Zirc (Clad) H20 reaction
  • Radiolytic decomp of H20
  • Corrosion of metals inside containment
27
Q

How is Air drawn into the H2 recombiner units?

A
  • natural convection. We ensure this happens by controlling the power to the units.
28
Q

What is the purpose of the Spray Add educator?

A
  • Draws the NaOH solution from the SAT and mixes it with a portion of the CTS pump discharge flow
29
Q

What must be closed before you can open ICM-305 and 306?

A
  • IMO-310/320 closed

- IMO215/225 closed

30
Q

When do the ESW to CTS Hx outlet valves throttle open and to what flow?

A
  • Throttle open on a CTS Signal and ICM 305/306 open to 2400gpm