CHW Flashcards
What is the purpose of the CHW system?
- The system provides 55°F chilled water at a nominal flow rate of 1550 gpm.
Where does the CHW head tank get its makeup water from?
Demin Water
What will happen if you select DISABLE on the HMI?
It will shutdown the entire system
What is the back make up water to the CHW head tank?
NESW
What is the normal power supply to Unit 1 CHW System?
Livingston Rd 12 Kv
What is the normal power supply to Unit 2 CHW System?
Transformer 10
What temp band is CHW trying to maintain in lower containment?
≥ 60° ≤ 120°
What temp band is CHW trying to maintain in upper containment?
≥ 60° and ≤ 100°
How long will the CHW chillers lockout due to rapidly lowering condenser cooling water temperature?
1 hr
With which color light requires an operator to don a SCBA if he needs to enter?
Red Light (High Level)
What pressure must be maintained according to LCO 3.6.4 (Containment Pressure)?
≥ -1.5# ≤ +0.3# (Modes 1-4)
What does TS LCO 3.6.4 A(Containment pressure) state?
If containment # is not within limits:
-WITH IN 1 HR
Restore containment pressure to within limits
What’s the warmest NESW (lake temperature) the plate hx can handle and still keep chw inlet temp to cnt at 55°?
53°