What are the NESW pump trips?

A
  • Overload
  • Overcurrent
  • Load Shed (Seq back on)
  • Load Conservation (CTS)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What NESW pump autostarts do you get when the switch is in Auto?

A
  • Low Header Pressure 55 psig (60 psig U2) (only when control switch in Auto)
  • SI
  • Load Shed
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Do the NESW pump discharge valves auto open on a manual start signal?

A
  • No, they have no auto features, must be manually opened after pump start
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

If the NESW pump switch is in auto, how must the discharge valve be arranged?

A
  • It must be open, since it does not auto open on its own when the pump starts.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

How soon after a Load Conservation can a NESW pump be restarted and how is it done?

A
  • It can be restarted after 75 secs by taking the pump switch to trip/lockout and back to on/run
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What are the NESW pump suction sources?

A

Both Units:

  • CW Intake Tunnel (Normal)
  • Discharge Tunnel (Alt)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What are the NESW pump power supplies?

A
  • 11/21C (N NSEW Pump)

- 11/21B (S NESW Pump)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Which NESW header has the glycol loads on it?

A
  • NESW Miscellaneous Header
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

When does WMO-906 (NESW Misc header supply valve) auto close?

A
  • On a Load Conservation
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

At what DP do the NESW Duplex strainers auto backwash at?

A
  • 76” H20
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

When do both units NESW Duplex Strainer backwash alarms come in?

A

95” H20 - Unit 1

97” H20 - Unit 2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What does T.S. 3.6.3 B (Cnt Isolation Valves) state?

A

If 2 CIV’s are inop
WITHIN 1 hr:
- Isolate penetration

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Which valves isolate on a load shed in the NESW system and why?

A

L.O. cooler WRV’s close:

  • maximizes flow the PAC, CAC, CLVs (If in Open Loop)
  • lowers load on EDG by lowering load on NESW
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Which unit’s NESW supplies the Seal Oil Coolers?

A
  • Unit 2
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Which unit’s NESW supplies the TSC Air conditioning?

A
  • Unit 1
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

When does the NESW header supply the Containment vent units, blowdown heat exchanger and blowdown sample heat exchanger?

A
  • When Containment Chill water is in Open Loop.
17
Q

What loads are on the NESW Misc Header?

A
  • Glycol Chillers
  • Ice Bin Cooling
  • Fluidizer Chiller Cndnsrs
  • Fluidizer Air Precoolers
  • Chem Cleaning Mix Tank
  • MUP
  • PHB BD Tank
  • Misc Sealing and Cooling
  • TRS Neutralization Ring Header
18
Q

What is cooled by the NESW Norm Header?

A
  • TSC Air Conditioning (U1)
  • Seal Oil Coolers (U2)
  • EHC Skid
  • MTLO Tank Coolers
  • MFP LO Coolers
  • PAC
  • CAC
  • Conductivity Room Sample
  • CHW Plate HX
  • CHW Solid Separators
19
Q

What NESW pump autostarts do you get when the switch is in neutral?

A
  • Load Shed

- SI

20
Q

What is the most important load on the NESW Misc Header?

A
  • Glycol Chillers
21
Q

What has to be done in order to reset the Lube Oil Cooler WRVs after a load shed?

A
  • All WRV Controllers have to be taken to minimum before you can push the reset button to get them to reset
22
Q

When do the LO Cooler WMOs get a close signal and when can they be operated after?

A

Load Conservation, they can be operated 75 sec after a load con

23
Q

Which Containment Isolation Valves don’t isolate on a Load Conservation?

24
Q

Which Containment Isolation Valves isolate on a Load Conservation?

A
  • CIR Vent Units
  • CUV Units
  • RCP Motor Air Coolers
25
Where is the NESW Header Pressure sensed?
- Downstream of the Strainer but before the Discharge check valve
26
What is the Power Supply to the NESW Motor outlet Valves?
600v AC
27
What is the Power Supply to the NESW Strainers?
600v AC
28
What occurs in the NESW Sys on a Load Conservation?
- Lube Oil Motor Op Valves (WMO’s) Automatically Close - NESW (inlet) CIV’s Automatically close: for CUV’s IR Vent Units, and MAC’s - Unit Crosstie Valve to Misc Header automatically closes (ie. Glycol) - NESW Pp trips W/CTS signal (Can be restarted after 75 sec by going to Trip/Lockout)
29
What occurs in the NESW System on a Loadshed?
- NESW Pp trips and Seq back on - L.O. cooler (WRV’s) close: which maximizes flow the PAC, CAC, CLVs - lowers load on EDG by lowering load on NESW
30
Which Containment NESW Load(s) DO NOT have Backup Air Bottle(s) for the CA to the NESW Cntmt Isol Vlv(s)?
RCP Motor Air Coolers CIVs
31
IF you have a CTS, then reset SI, NESW pumps which were NOT running prior to event will?
Restart unless locked out.