Radwaste Building HVAC Flashcards
What does the Radwaste Building HVAC do?
-Maintain Ventilation in process equipment areas
-Provide personnel safety access areas
-Restrict spreading of airborne radioactivity
What does Radwaste Building HVAC consist of ?
-Radwaste building supply
-Radwaste Building Exhaust air system
-Radwaste Building Control Room recirculation
How many Radwaste Building Normal AHUs are there? What do they do ?
-There are two normal AHU
-They condition outside air for Radwaste Building
What is the evaporator cooling pad & evaporative Recirc. Pump used for on the Radwaste Normal AHU ? Where does it get water from ?
-Level is maintained by float level & uses domestic water to
-Water is pumped from evaporative module Recirc pump to top of evaporative cooling pad
What does the RU-14 monitor ?
Samples & monitors radioactive particles &noble gasss exhausted from Radwaste Building
What does the RU15 monitor ?
Monitors combined exhaust from Waste Gas system area
What do RU-143 & 144 monitor?
Monitors plant vent
How would the BAC be affected if Radwaste Building AHU& AFU are lost ?
Could impact BAC releases which causes exhaust humidity set point to exceed
What happens if Radwaste exhaust humidity set point is exceeded?
BAC release flow rate would need to reduced to low humidity
What happens instrument air going to damper drops below 30psig ?
Dampers will fail close & will trip fans on thermal overload