Instrument Air(IA) Flashcards
What’re the differences in Instrument Air & Service Air ?
Instrument Air- 125psig for pneumatic instrument operation & pneumatic actuators
Service Air- 125psig for pneumatic tools,resin transfer,refueling machine,& manual operation
Why is instrument air a safety related system ?
All AOVs will fail into there fail-safe position to safely shut plant down
What’re the capacity of the 3 compressors for the IA system ?
Three 100% capacity air compressors
When will LP Nitrogen automatically align to IA header ?
Will automatically align when IA header pressure goes down to 85psig
Where do the air compressors draw their air from ? What does it compress it down to ?
-Draws air from turbine building & compresses it down to 105-123psig
What size are the Inlet Air Filters for the compressors ?
Removes particles 3micron or larger 99.9% effective
What does the PT-4 pressure sensor represent ?
-Represents Inlet Filter cleanliness, calibrated to read 0psig for Atm. Press.
-Will sense lowering pressure(rising vacuum)
What does local controller PT-4 Inlet Vacuum information to do what ?
-Confirm drive motor is rotating in correct direction upon start
-Indicate condition of Inlet Air Filter
-Provide logic for positioning inlet valve during unloaded operation based on coolant injection temp &separator press.
What is the Air Inlet Control Valve opened & closed by ?
-Open & closed by a stepper motor, which is control by Intellysis Controller
What does the Intellysis Controller do ?
Regulated stepper motor to position Air Inlet Control Valve based on demand plant air system
During compressor startup why is the Air Inlet Control Valve closed ?
-Allows compressor to startup with minimum current
-Allows compressor to check for proper rotation by checking Inlet Vacuum is at 1psi within 2seconds
What will happen if Air Inlet Control Valve fails to open & close during startup?
This will cause an alarm
How does “loaded operation” work ?
-The Intellisys/stepper motor opens inlet valve & closes blowdown when plant pressure drops below Min. Setpoint of 109psig
-Then compressor will start to deliver air to plant system
How does “unloaded operation” work ?
-Plant air reaches Max. Press. of 119psig then Inlet valve will slightly close
-Blowdown will open
-Compressor will be at Min. Power
-Intellisys controller will maintain Inlet Valve open to maintain pressure
What pressure do the Compressors compress to ? What’re the compressors driven by ?
-They compress press. between 105-123psig
-Driven by 480VAC motor driven
Where do the compressors discharge to ?
-They discharge into separator tank