Extraction Stea & Drains(ED) Flashcards
What does the Heater Drain Tank provide for the Extraction Steam system ?
-Ultimate drain point for most of the normal drains in ED system
-Provides suction source for the HTR Drain Pumps
Where does the HTR Drain Pumps discharge to ?
-Discharges to suction of the associated Main FW Pump
How is flow regulated to the Main FW Pump suction ?
-Regulated by HTR Drain Tank level to ensure it has enough water for HTR Drain Pump
-Mini flow back to HTR Drain Tank is provided for each HTR Drain Pump
How many HTR Drain Pumps are there? Where do they take suction from ?
There are two HTR Drain Pumps, that have there own HTR Drain Tank to take suction from
What powers the HTR Drain Pumps ?
-NBN-S01 powers ‘B’ HTR Drain Pump
-NBN-S02 powers ‘A’ HTR Drain Pump
THINK OPPOSITE
Where is seal water provided from for HTR Drain Pumps ?
Provided from Condensate Header at 375-500psig
Where is cooling water for the HTR Drain Pumps stuffing box provide from ?
Provided from condensate service header at 50-100psig
What is the HTR Drain Pump mini follow valve positioned by ?
Positioned by HTR Drain Pump flow transmitter to maintain minimum flow through HTR Drain Pump
What happens to the HTR Drain Pump mini flow valve when unit comes up in power & has more extraction steam flow available to pump ?
Mini flow valve will close
When will stop the HTR Drain Pumps ?
-HTR Drain Tank LO-LO level alarm
-HTR Drain Pump low flow after time delay
-Electrical protection
Where does flow from the HTR Drain Tank go when the High Level Control Valve actuates ?
Directs high energy fluid to condenser
Why is it bad for flow from the HTR Drain Tank High Level Control Valves to actuate ?
It’s bad on the tube because it causes high vibration & erosion in tube bundle due to velocity & thermal changes when entering condenser
What just be done to minimize high level control valve to be activated ?
Reducing power to 50% until HTR Drain Trains are cross-tied
Why is having a cross connected HTR Drain Pump important , when a High Level Control Valve actuates ?
Reduce HTR Drain Tanks High Level Control Valve actuation <25%
How many HP Feedwater Heaters trains are there ?
-There are two parallel trains of HPFWH
Why does the #5 HPFWH not have a level control system ?
It doesn’t contain a drain cooler region