Fire Protection Flashcards
What’re the 3 subsystems for Fire Protection system ?
-Fire Protection - Chemical system
-Fire Protection- H2O System
-Fire Detection & Alarm System
What’re the functions of the Fire protection chemical system ?
-Detect,Contain, & extinguish fires in areas where water is impractical
-Assure availability of at least one safe shutdown path
-Minimize loss of life & property
What’re the functions of Fire protection H2O system ?
-Maintain reliable source of water to extinguish fired inside power block
-provide water flow & pressure to supply hose hydrants for manual firefighting
- Provides water flow & pressure when wet pipe/or pre-action sprinkler
What’re the functions of Fire Detections and Alarm Systems ?
-Provide fire/smoke detection for areas that contain or present potential fire exposure to related equipment
-Initiate visual and audible alarms to warn plant personnel of fire/smoke
What’re the properties that make CO2 such a good fire extinguishing agent ?
1.)Non-combustible
2.)Non-reactive
3.)Non-Conductive
What’re CO2 extinguishers used for ? Where are areas that CO2 flooding systems are commonly used for ?
-They’re used for suffocation & cooling
-They’re used in unoccupied areas and contains equipment vulnerable to both fires and water spray damage
What’re areas in plant that have CO2 flooding system ?
-Battery rooms A-D
-ESF switchgear room (A/B Train)
-SBOGS to extinguish fire
-
How would CO2 be deployed in the non class switchgear room ?
-CO2 would get deployed from hose reels manually by fire department
-Hose reels get the CO2 from the same storage tank and all other CO2 systems
What’re the dangers of CO2? What is used to let people know CO2 is about to be used ?
-CO2 displaces oxygen in the area & bloodstream, leads to unconsciousness or death
-Pre alarm will sound before CO2 is dispersed so people can get out the area
What must happen for CO2 to be auto dispersed ?
-CO2 is initiated when crosszones one smoke & one thermal fire detector are actuated
What’re the pre-alarms for CO2 flooding ?
First alarm- Bell sounds when one detection zone actuates
Second alarm- Pre-discharge alarm for personnel safety to leave area
-Wintergreen odorant also to warn people after CO2 is discharged
What must be worn when using the CO2 Hose reels?
SCBA & turnout gear must be worn, which makes this a Fire Department function
Where is the CO2 source located at ?
Low Pressure storage vessel located in each power block by radwaste building
What else does CO2 supply vessel used for in the plant ?
-CO2 is used to purge the main generator
- Lower portion of the vessel is dedicated to fire protection
What’re properties of Halon that make it’s a desirable Fire extinguisher?
.Non-toxic
.Non-Conductive
.Leaves little corrosive residue
Where type of areas is Halon usually used in ?
-Both occupied and unoccupied areas
-Areas vulnerable to both Fire and Water spray damage
What areas in the control building does Halon system provide fire protection to ?
-Remote Shutdown Rooms
-Inverter room
-Computer Room
-Communications room
How is automatic release of Halon initiated ?
-Activation of Two ionization detectors arranged in cross zone manner
-Specifically for remote shutdown room, a temp. rate of rise detector will also initiate halon flooding
What’re the alarms that’ll be used when detectors are actuated ?
First alarm - Early detection alarm that registers locally and at control room computer console
Second alarm- isolates room from HVAC system using fire dampers
-Also actuates pre-discharge alarm,which results in discharge of Halon
What’re ways to manually discharge Halon ?
-Operating Pull Station handle or by manual actuation at halon storage cylinder
What components does a Halon system have ?
-Storage container cylinders
-Control Valve
-Piping
-Spraynozzle
-Detection and actuation system
-Alarms
-Manual Pull station
What’re the components for Fire protection -Water system ?
-Water storage Tanks
-Fire Pumps
-Jockey Pump
-Fire Main Header
-Hydrants
-Hose Stations
-Sprinkler system
What’re features of the water storage tanks ?
-Two water storage tanks located at WRF
- Tanks are supplied from a deep well pump
How many pumps do we have for Fire Protection ?
-Three 50% capacity fire pumps
-Jockey pump to maintain header pressure with no loads on system
What’re the spacing between fire hydrants? What’re the Hose lengths that are used ?
-Fire hydrants spaced in 250ft intervals
-Fire hose connections all over building
-75ft hoses used in normally accessible areas
-Isolated cases are permitted the use of 100ft hose lengths
What’re the 3 types of sprinkler systems ?
-Wet pipe
-Deluge
-Pre-Action