Non Class 120VAC Instrument Power(NN) Flashcards
What kind of power does 120VAC instrumentation power supply ?
Single phase, 60hertz, regulated, and filtered power to four subsystems
What’re the subsystems that get powered by NN system ?
NNN-D11;NNN-D12;NNN-D15;
NNN-D16
What kind of equipment is in each subsystem ?
Normal/backup supply voltage regulators
A static switch between the voltage regulator supplies
What is the normal power for the NN system ?
Non class MCC
What is the emergency power supplies for NN system ?
D11&D12:Separate Class VAC MCC
D15&D16:Separate non class 480VAC SIAS load shed MCC
What’re the 3 positions on manual bypass switch ?
Manuel transfer to normal/Automatic/ Manual Transfer Emergency
How do the indicating lights work on static switch ?
Green:normal source
RED: emergency source
What must happen to switch bypass switch to “AUTO” position ?
Break and make (will lose power to loads temporarily as you switch it back to auto )
What is voltage regulating transformer for?
Step down voltage from 480VAC to 120VAC & to filter out transients from primary side to maintain steady output voltage on secondary side
What is Voltage Regulating Transformer designed for ?
Designed to accept varying AC input voltage (+-15%rated),output voltage is well regulated filtered AC output; filters out transients from primary side to secondary side
What does NNN-D11& NNN-D12 provide power for ?
Reactor control instru. & other station service loads
.FW control system
.Steam bypass control system
. CEDMCS
.Fuel pool instru.
.RCS&CVCS process instru.
What did NNN-D15& NNN-D16 provide power to ?
Balance of Plant (BOP) & miscellaneous station service loads
.Plant annunciator cabinets
.Ground detection circuitry
.Control oil for turbine trip
What kind of equipment does the Ground detection system have on D11&D12 ?
Ground detection relay, RED ground light, and reset push button
What happens on loss of power to NNN-D11 ?
.CD: pump “B” mini flow fail open
.CH: letdown is lost
.RC:loss of PZR pressure control
.Reactor control(SF):reactor power cutback is disabled ; steam bypass valve failed closed
What happens on loss of power to NNN-D12?
.CD makeup and draw off valves failed closed
.demons fail into full flow
.CD pumps A&C mini flow fail open
.level indication and makeup to (VCT)
.letdown lost
.loss of automatic control rod control