Non Class 120VAC Instrument Power(NN) Flashcards

1
Q

What kind of power does 120VAC instrumentation power supply ?

A

Single phase, 60hertz, regulated, and filtered power to four subsystems

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What’re the subsystems that get powered by NN system ?

A

NNN-D11;NNN-D12;NNN-D15;
NNN-D16

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What kind of equipment is in each subsystem ?

A

Normal/backup supply voltage regulators
A static switch between the voltage regulator supplies

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is the normal power for the NN system ?

A

Non class MCC

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What is the emergency power supplies for NN system ?

A

D11&D12:Separate Class VAC MCC
D15&D16:Separate non class 480VAC SIAS load shed MCC

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What’re the 3 positions on manual bypass switch ?

A

Manuel transfer to normal/Automatic/ Manual Transfer Emergency

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

How do the indicating lights work on static switch ?

A

Green:normal source
RED: emergency source

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What must happen to switch bypass switch to “AUTO” position ?

A

Break and make (will lose power to loads temporarily as you switch it back to auto )

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What is voltage regulating transformer for?

A

Step down voltage from 480VAC to 120VAC & to filter out transients from primary side to maintain steady output voltage on secondary side

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What is Voltage Regulating Transformer designed for ?

A

Designed to accept varying AC input voltage (+-15%rated),output voltage is well regulated filtered AC output; filters out transients from primary side to secondary side

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What does NNN-D11& NNN-D12 provide power for ?

A

Reactor control instru. & other station service loads
.FW control system
.Steam bypass control system
. CEDMCS
.Fuel pool instru.
.RCS&CVCS process instru.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What did NNN-D15& NNN-D16 provide power to ?

A

Balance of Plant (BOP) & miscellaneous station service loads
.Plant annunciator cabinets
.Ground detection circuitry
.Control oil for turbine trip

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What kind of equipment does the Ground detection system have on D11&D12 ?

A

Ground detection relay, RED ground light, and reset push button

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What happens on loss of power to NNN-D11 ?

A

.CD: pump “B” mini flow fail open
.CH: letdown is lost
.RC:loss of PZR pressure control
.Reactor control(SF):reactor power cutback is disabled ; steam bypass valve failed closed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What happens on loss of power to NNN-D12?

A

.CD makeup and draw off valves failed closed
.demons fail into full flow
.CD pumps A&C mini flow fail open
.level indication and makeup to (VCT)
.letdown lost
.loss of automatic control rod control

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What happens if you lose power to NNN-D15& D16?

A

Main feedwater pumps speed drops to about 300rpm, which will lead to reactor power cutback

17
Q

Where are the NN distributions panels located ?

A

D11&12:120ft control building
D15:100ft of turbine building
D16:120ft of Aux building