Radioactive Drains Flashcards

1
Q

Where does the Reactor Cavity Sump collect leakage from ?

A

Collects leakage & condensate from Reactor Cavity & Excore Instrumentation

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

The max volume of the Reactor Cavity Sump is 520gallons, what should the operation of the both sump pumps be ?

A

At that volume both sump pumps should be operating

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Where does the Reactor Cavity Sump vent to ?

A

It’s vents to containment building atmosphere

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

When will control room alarm be activated for the Reactor Cavity Sump ?

A

-Generated on high level or if level increases greater than 1gpm for 1hr
-Also may alarm on excessive Sump Pump run time

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Where do the Reactor Cavity Sump pump to ?

A

Pumps liquid from Reactor Cavity Sump to the East Containment Sump

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Where are the Reactor Cavity Sump Pumps powered from ?

A

They’re powered from 480VAC MCC(NH)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Where do the Containment East & West Radwaste Sumps collect from?

A

Collects leakage & condensed liquid inside containment

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Where does West Sump receive effluent from inside containment?

A

-Floor drains
-Equipment Drains
-Refueling Pool
-Refueling Pool linear plate detector compartment

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What’re the two penetrations on the East Sump receiving effluent from ?

A

One of them is for:
-Floor Drains
-Equipment Drains
-Refueling Pool
Second is from:
-Reactor Cavity Sump Pumps

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

When will an alarm actuate inside control room East & West Sump?

A

-Generated on high level or has inflow greater than 1gpm for one hour
-Has abnormal excessive sump pump run time

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What’re the Containment Radwaste Sump Pumps used for ?

A

Pumps Containment Sump contents out of containment to Liquid Radwaste TDS Holdup Tanks

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What should you do during unusual run time containment sump ?

A

You should report it to the control room

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Where is Containment Sump run time displayed at ?

A

Displayed on MCC Breaker & logged on shifting basis

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Why do the ESF Equipment Room have separate drainage system ‘A’ & ‘B’ trains ?

A

So that if one ESF room of one train is flooded it won’t jeopardize the other train

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Where do the ESF ‘A’ & ‘B’ train drainage systems drain to ?

A

They drain to there own independent segregated sumps

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What are the penetrations for each ESF Sump ? Where does each sump vent to ?

A

-SDCHX
-CS Pump Room
-HPSI Pump Room
-LPSI Pump Room
-Pipe Chase
-Vents to Aux. Building HVAC Exhaust

17
Q

What’re the ESF Sump Pumps used for ?

A

Used to transfer ESF Sump contents to Liquid Radwaste TDS Holdup Tanks

18
Q

What’re the ESF Sump Pumps lubricated by ?

A

Lubricated by Demineralized Water

19
Q

What kind of capacity do the ESF Sump Pumps have ?

A

They both have 100% capacity

20
Q

Where does the penetration into the Non-ESF Sump come from ? Where is it vented to ?

A

-It comes from floor drains & equipment drains throughout the Aux. Building
-Also Equipment Drain Tank relief valve relieves into sump
-Vented to Aux. Building HVAC Exhaust

21
Q

What’re the Non-ESF Sump Pump used for ?

A

Pump sump contents to liquid Radwaste

22
Q

What happens when Charging Pump Oil Drain Tank becomes full ?

A

Oil is pumped into a 55gallon drum & rest of water is drained into Radwaste Building Sump

23
Q

What’re the four pipe penetrations into the Fuel Building Sump ? Where does Fuel Building Sump vent to ?

A

-Floor drains & equipment drains
-Cask Decontamination pit
-Fuel Pool Linear Plate Leak Detector Compartment
-Cask Pit

-Vents to Fuel Building atmosphere

24
Q

What’re the pipe penetrations into the Holdup Tank Area Sump ?

A

-RMWT
-CVCS Holdup Pump Room
-Refueling Water Tank
-CVCS Holdup Tank Overflow

25
Q

Where do the Decon. & Laundry Facility Sump Pumps deliver water to ?

A

They pump sump contents to the LR Chemical Drain Tanks

26
Q

Where are the hand switches for Containment Sump Pumps located ?

A

Located in Control Room on B07

27
Q

What is used to equalize run time for sump pumps ?

A

An alternator is used to switch between the two pumps

28
Q

When will pump start/ stop when switch is placed in AUTO?

A

-Will start on sump HI level
-Will stop on sump LO level

29
Q

When a sump pump starts, what else must start ?

A

Bearing cooling water supply solenoid valve must be energized to provide Demon. Water for lubrication

30
Q

What happens if a HI-HI sump level is reached ? What will happen in control room on HI-HI sump level ?

A

-It will actuate the standby pump to run
-HI-HI Sump LVL will alarm B07 in Control Room

31
Q

What happens in Radwaste Control Room when Radwaste Building Sump level HI-HI?

A

Radwaste control room will alarm

32
Q

What happens if sump has LO-LO level on LSLL ?

A

Any running sump pump will be stopped on LO-LO level

33
Q

What could happen on a loss of Radioactive Drain system ?

A

-If pumps didn’t work sumps would overflow causing radioactive spill
-If level gets high enough it could cause loss of safety equipment