Station Power Alarms Flashcards
What is EK-0325, “UNIT TRANSFORMERS TROUBLE”
Sensor:
- 474 TXM (Main Transformer)
- 274 TX (Station Power 1-1)
- 174 TX (Station Power 1-2)
Trip Setpoints: Any annunciation at local panel on Main, Station Power 1-1, or Station Power 1-2 Transformers
Alternate Indication: None
EK-0325 does NOT have Reflash. Additional monitoring will be required when standing alarm conditions exist.
What is EK-0530, “START-UP TRANSFORMERS TROUBLE”
Sensor:
- 474 TX-S1 or 474 TX-S2
Trip Setpoints:
- Any alarm on local alarm Panel: EK-X03 (Startup Transformer 1-1) or
- EK-X04 (Startup Transformer 1-2)
Alternate Indication:
- Red Trouble Light for Xfmr Start-up 1-1EX-03 or Xfmr Start-up 1-2 EX-04 (EC-04)
What is EK-0525, “START-UP TRANSFORMERS TRIP”
Sensor:
- 486-11 (S/U XFMR 1-1) or 486-12 (S/U XFMR 1-2)
Trip Setpoints:
- From Differential, Sudden Pressure, Overcurrent, or Ground relays
Alternate Indication:
- Voltage indication for affected buses
AUTOMATIC FUNCTION:
Affected Startup Transformer Incoming Breakers trip, if closed:
o Startup Transformer 1-1: 252-102 (Bus 1A), 252-302 (Bus 1F)
o Startup Transformer 1-2: 152-106 (Bus 1C), 152-202 (Bus 1D), 152-303 (Bus 1E)
‘R’ Bus trips.
What is EK-0529, “START-UP TRANSFORMER PROT CKT UNDERVOLTAGE”
Sensor:
- 474S
Trip Setpoints:
- Loss of Potential
Alternate Indication:
- Loss of D11-1 indicated by auto start of Steam Driven Auxiliary Feedwater Pump P-8B
What is EK-3304, “STARTUP TRANSFORMER NO 1-3 TROUBLE”
Sensor: 474TX-S3
Trip Setpoints: Any alarm on local alarm panel EK-X091 on S/U XFMR 1-3
Alternate Indication: None
What is EK-3303, “STARTUP TRANSFORMER NO 1-3 TRIP”
Sensor: 486-13
Trip Setpoints: From Differential, Ground, Sudden Pressure, and Overcurrent relays
Alternate Indication: “R” Bus tripped
Trips “R” Bus
Trips breaker 252-202 4160V Bus 1B Startup Transformer 1-3 Incoming Breaker
Trips breaker 252-402, S/U XFMR 1-3 to Bus 1G
What is EK-3301, “START-UP TRANS NO 1-3 PROT CKT UNDERVOLTAGE”
Sensor:
- 474-S3
Trip Setpoints:
- 52 VDC
Alternate Indication:
- Bus 1A “Control Power Available” light on Panel C-04
What is EK-0326, “STA POWER TRANSFORMER 1-1 SUDDEN PRESS”
Sensor:
263X, Sudden Pressure Alarm Trip, Deluge Control (2 of 3 logic)
263X3, Sudden Pressure Alarm Deluge Control
Trip Setpoints: No specific setting
Alternate Indication: None
What is EK-0332, “STA POWER TRANSFORMER 1-2 SUDDEN PRESS”
Sensor: 163X Relay (2 of 3 logic)
Trip Setpoints: No specific setting
Alternate Indication: None
AUTOMATIC FUNCTION:
Trips 386P, Generator Direct Trip Lockout Relay, which trips Generator Breakers 25F7 and 25H9.
Initiates Transformer deluge.
What is
- EK-3339, “STA PWR TRANS NO 1-3 SUDDEN PRESSURE”
Sensor: 30/K4B
Trip Setpoints: No specific setting
Alternate Indication: None
AUTOMATIC FUNCTION:
Trips 386P Lockout Relay, which trips Generator Breakers 25F7 and 25H9.
● Initiates Transformer Deluge.
What is
- EK-0331, “MAIN TRANSFORMER SUDDEN PRESS”
Sensor: 463X Relay (2 of 3 logic)
Trip Setpoints: No specific setting
Alternate Indication: None
AUTOMATIC FUNCTION:
Trips 386P, Generator Direct Trip Lockout Relay, which trips Generator Breakers 25F7 and 25H9.
Initiates Transformer deluge.
What is
- - EK-0526, EK-0527, “START-UP TRANSFORMER NO 1-1 (1-2) SUDDEN PRESS.”
Sensor: 463X-11
Trip Setpoints: No specific setting
Alternate Indication: Voltage indication for affected bus & ‘R’ Bus trip indications
AUTOMATIC FUNCTION:
Trips Lockout Relay 486-11, actuating EK-0525 “Startup Transformers Trip.”
Affected Startup Transformer Incoming Breakers trip, if closed:
o Startup Transformer 1-1: 252-102 (Bus 1A), 252-302 (Bus 1F)
‘R’ Bus trips.
Transformer Deluge initiated.
What is EK-3302, “STARTUP TRANSFORMER NO 1-3 SUDDEN PRESS”
Sensor: 463X-13
Trip Setpoints: No specific setting
Alternate Indication: None
AUTOMATIC FUNCTION:
Trips 486-13 lockout relay, actuating Annunciator # 3.
Initiates Transformer deluge.
What is EK-0329, “PILOT WIRE TROUBLE”
Sensor: PM 13-1 Relay
Trip Setpoints: Loss or Failure of DC Monitoring Current
Alternate Indication: None
What is EK-0330, “SWYD PWR PLT INTERPOSING CONTROL CKT UNDERVOLTAGE”
Sensor:
- 474-1, Interposing Control 25F7
- 474-2, Interposing Control 25H9
- 474-3, Control Circuit Undervoltage
Trip Setpoints: Loss of DC Voltage
Alternate Indication: None