Main Condenser, Condensate and Feedwater Flashcards
What is the purpose of the main condenser, condensate and feedwater system?
Recover and preheat condensate for reuse as steam generator feedwater
Is the main condenser, condensate and feedwater system safety related.
Not safety related.
Safety Related Function
- CHP or SG Low Pressure
- Close Feedwater Regulating Valves and Bypass Valves
What is the flow path of the Main Condenser, Condensate and Feedwater System?
- Steam exhausts from LP turbines into the Main Condenser where it makes a single pass around the tube bank area to be condensed and de-aerated.
- Condensate Pumps take suction on hotwell and discharge to a common line that splits in two passes in parallel through the air ejector condenser and the gland seal condenser.
- Piping taps off to CV-0730, Condensate Recirc Valve, and recircs to Main Condenser when system flow is low.
- The flow recombines into a common line and then splits and is routed through Drain Coolers E-7A and E-7B and through LP feedwater heaters E-1A-4A and E-1B-4B.
- Flow from the LP heaters passes through HP Feedwater Heaters E-5A and E-5B and is crosstied at the suction header of the Main Feed Pumps (MFPs) where it combines with P-10 A/B, Heater Drain Pumps discharge.
- MFPs discharge through the Feedwater Regulating Valves and/or Feedwater Regulating Valves Bypass Valves and through HP Feedwater Heaters E-6A and E-6B to the SGs. ‘A’ pump feeds ‘B’ SG and vice versa.
- MFP Recirc Valves are just upstream of the Feedwater Regulating Valves and direct recirculation flow to Main Condenser when system flow is low.
- Hotwell makeup gravity feeds from T-2, CST, via 3” Makeup Valve CV-0732, 6” Makeup Valve CV-0729, or 12” Makeup Bypass Valve CV-0733 (normally Isolated).
- Hotwell rejects from the inlet of the air ejector and gland seal condensers to T-2 through Reject Valve CV-0731.
- From memory, draw and label a one line diagram of the Main Condenser, Condensate and Feedwater system showing system interfaces and the following major components:
- Hotwell
- Condensate Pumps (P-2s)
- Gland Seal Condenser
- Air Ejectors
- Feedwater Heaters (E-1s - E-5s)
- Drain Cooler (E-7s)
- Main Condensate recirc line to the Hotwell
- CV-0730 (Recirc CV)
- Heater Drain Pumps (P-10s)
- Feedwater Heaters (E-6s)
- Main Feed Pumps
- Main Feed Reg Valves
- Main Feed Reg Bypass Valves
- Steam Generators
in accordance with P&ID M-207. (056 K1, 059 K1)
DRAW
What could be the cause of lowering vacuum in the main condenser?
- Reduction in circulating water flow
- Increase in circulating water temperature
- Air inleakage in excess of the SJAEs
- Air inleakage may also raise secondary system oxygen levels above limits.
Could lead to a Main Turbine trip.
What is the result of condenser tube leakage? What happens if a waterbox is removed from service?
Tube Leakage
- Increase in secondary side oxygen levels.
Waterbox removal
- Derate to <55%
What are the indications and at what level is the hotwell normally maintained?
Hotwell level indication
- LI-0729 on C-01
Normal Level
- ~ 66% to 71% to ensure Condensate Pump NPSH
What is the normal hotwell fill?
Normal make-up
- Automatic via 3” Makeup Valve CV-0732.
- Modulates open at 66%.
What are other methods beyond the normal for filling the hotwell?
Six-Inch Makeup
- CV-0729 (manual) from the control room, via Yokagawa controller thumbwheel
- Blue pen is signal to CV-0729.
- Red pen not used.
12-Inch Makeup
- CV-0733 automatically opens on low level @ 58%.
- Designed to compensate for Atmospheric Steam Dump operation.
- Normally isolated as an Appendix R requirement.
How is hotwell reject handled?
Hotwell Reject
- 4” Condensate Reject Valve CV-0731
- Modulates open automatically at 76%.
- Rejects flow in excess of makeup capability of the combined 3” and 6” makeup valves.
What is a concern with the hotwell reject valve?
Valve operates only by the level controller and cannot be closed by the operator.
- Open failure
- Condensate Pump damage
- and/or T-2 damage due to overfilling.
What is the power supply, discharge pressure and flow of the condensate pumps?
Discharge Flow and Pressure
- 9250 gpm each
- Minimum is approximately 1400 gpm each
- Approx 500 psig
P-2A - Alpha Bus
P-2B - Bravo Bus
What and why is the power limit for operation with one P-2, Condensate Pump?
- Plant power level is limited to < 30%
- Prevents challenging the MFP low suction pressure trip.
What are the Condensate Pump starting limits?
2 starts allowed in succession with the motor initially at room ambient temperature, OR 1 start with the motor at a temperature not exceeding normal operating temperature.
WHEN P-2 motor has been running continuously for > 30 minutes OR idle for > 60 minutes, THEN it is considered to be not exceeding normal operating temperature
What are the Condensate Pump controls, indications and normal parameters?
Controls
- Four position switch for each pump on C-01.
- Trip
- Close
- Normal After Trip
- Normal After Close
Light Indication
- Green Light for OFF
- Red Light for RUN
Indications
- Motor amps: Normally 325 to 375 amps
- Motor winding temperatures: 200° to 220°F
- Motor thrust bearing temperature: 100° to 125°F
What is Condensate Recirc Control Valve CV-0730?
Condensate Recirc Control Valve CV-0730
- Dowstream of Gland Seal Exhauster and SJAE
- 12” valve modulates on a flow signal from FC-0730
- Maintains minimum flow for Condensate Pumps
- Minimum flow of 6800 gpm
- 1600 gpm through the gland seal condenser
- 5200 gpm through the air ejector condenser
- Minimum flow of 6800 gpm
What are the indications for CV-0730, Condensate Recirc Control Valve?
Red and green position indicating lights on C-01
- Dark Stroke
Fails closed on loss of air.
Downpower
- Should start opening at approximately 25% power
Power Escalation
- Should be full closed at 35 to 40% power
What happens if CV-0730 fails to open?
As long as a feedwater pump is still operating there is no concern for CV-0730 failing to open as the feedwater pump recirculation valve will be open maintaining an adequate flow path for the condensate pumps.
Discuss the FW heaters in terms of design and pressure?
E-7A/B
- Drain Coolers - Full of Water on both shell and tube side
E-1A/B through E-4A/B
- Low Pressure Heaters
- Shell is Extraction steam/Condesate
- Tube is Feedwater
E-5A/B - E-6A/B
- High Pressure Heaters
- Shell is Extraction steam/Condesate
- Tube is Feedwater
How are feedwater heaters bypassed?
- E-7A (B), E-1A (B), and E-2A (B) must be isolated and bypassed together.
- E-3A (B) and E-4A (B) must be isolated and bypassed together.
- Although E-5A (B), and E-6A (B) can be isolated individually, administratively they must be isolated and bypassed together.
What are the main feed pump discharge, pressure, flow, etc.?
- 13,600 gpm
- Total discharge of 831 psi when operating at 5000 rpm
- Turbine drivers rated at 7000 HP at 5000 rpm
- HP Steam Supplied at < 30% power
- LP Steam at power >30% power
What are the main feed pump permissives?
Suction valve for associated pump open. Open limit switch POS-0787 (POS-0788) made up.
Main Condenser vacuum PS-0583 (PS-0586) ≥ 15” Hg