CRHV Flashcards
Explain the purpose of the Control Room HVAC System
Maintain the
- Control Room
- Tech Support Center
- Viewing Gallery
- and Mechanical Equipment Room environments
Suitable for continuous personnel occupancy and reliable equipment operation under all conditions
Is the control room HVAC safety related?
NO
What are the functional capability and design features of the CRHVAC?
- Maintained at a positive pressure (vestibule doors part of this).
- Limit radiation exposure of Control Room Personnel during any of the postulated DBA(s) within the guidelines of 10CFR50, Appendix A, General Design Criterion 19.
- Single active component failure, even with loss of off‑site power, cannot impair the system’s ability to meet its design function.
- Permits rapid purging of smoke.
- Remain functional during and after earthquake (seismic).
- Remain functional during and after a design basis tornado.
- Maintain temperature and humidity within recommended comfort zone.
- Permit periodic inspection, testing and maintenance.
What components make up the over overall CRHVAC system?
Two trains of
- Air Handling/Filtering Units
- Continuous Air Monitor (CAM) Units
- Purge Exhaust System
- Toilet Exhaust System, and
- Associated ductwork, dampers, instruments and controls.
What are the major components of the ‘A’ train of CRHVAC?
Air Handling Unit V‑95
Condensing Unit VC-11
Continuous Air Monitor Unit RIA-1818A
Charcoal Filter Unit VF-26A
Fan V-26A.
What are the major components of the ‘B’ train of CRHVAC?
- Air Handling Unit V‑96
- Condensing Unit VC-10
- Continuous Air Monitor Unit RIA-1818B
- Charcoal Filter Unit VF-26B
- V-26B.
How does Recirculation Mode for CRHVAC impact RIA-1818A/B’s monitoring capability?
RIA-1818A/B are not located in the recirculation flow path thus will not detect adverse radiological conditions.
How does Recirculation Mode for CRHVAC impact pressure in the Control Room Envelope?
CRE will depressurize due to lack of makeup air.
How is Recirculation Mode initiated?
Initiated by placing DPIC-1659 (DPIC-1660) in manual and closing Damper D-2 (D-9).
What is the normal flow path for CRHVAC?
- Outside air is drawn in through a normal outside air intake
- Tornado Damper TD-1 (TD-2)
- Normal Air Intake Damper D-1 (D-8)
- Modulating Damper D-2 (D-9)
- Recirculation Damper D-3 (D-10) open, Recirculation Damper D-6 (D-13) closed
- Air discharges into Control Room Envelope
- Toilet Exhaust Fan V-16 discharges air through Exhaust Dampers D-17 & D-18 and Tornado Damper TD-6
What is the recirculation flow path?
- Modulating Damper D-2 (D-9) is closed
- Recirculation Damper D-3 (D-10) open
- Recirculation Damper D-6 (D-13) closed
- Air discharges into Control Room Envelope
- Toilet Exhaust Fan V-16 discharges air through Exhaust Dampers D-17 & D-18 and Tornado Damper TD-6
What is the flow path for purging?
- Purge Fan V-94 is started
- Purge Exhaust Dampers D-15 & D-16 open, Recirculation Damper D-3 (D-10) closes
- Control Room Differential Pressure Controller DPIC-1659 (DPIC-1660) modulates damper D-2 (D-9) as necessary to control pressure
What is the Emergency Flow Path?
- Verify Air Handling Unit V-95 (V-96) in service
- Air Filter Unit Fan V-26A (V-26B) in service
- Outside air is drawn in through emergency air intake through Tornado Damper TD-4 (TD-5) and Emergency Air Inlet Damper D-7 (D-14)
- Discharge Damper D-5 (D-12) opens
- VHX-26A (VHX-26B) heater energizes
- Dampers D-20 (D-21) modulate to control flow
- Normal Air Inlet Dampers D-1 & D-2 (D-8 & D-9) close
- Recirc Dampers D-3 & D-6 (D-10 & D-13) open
- Exhaust Fan V-16 trips if running, Dampers D-17 & D‑18, TD-6 close
- Purge Fan V-94 trips if running, Dampers D-15 & D‑16 close
How do CHP and CHR impact CRHVAC?
CHP (2 of 4 at 4 psig)
CHR (2 of 4 at 10R)
- CRHVAC goes to Emergency
- Condensing Units VC-11/VC-10 if operating will trip
Explain why a positive pressure is maintained in the Control Room, Viewing Gallery, TSC, and Mechanical Equipment Room.
Prevents airborne radioactive material from entering the controlled area subsequent to accidents.
Differential Pressure Transmitter DPT-1659 (DPT-1660)
- Compares Control Room pressure with South Corridor
- Modulates damper D-2 (D-9) on the air inlet to maintain dp at 0.125” H2O
What is the design and operation of Air Handling Units V-95 (V-96)?
Each air handling unit consists of the following
- A medium efficiency filter
- Efficiency – 60 to 65%
- An electric heating coil
- Breaker open - not needed
- MCC-77 (MCC-78)
- A refrigerant cooling coil
- 11,340 CFM of recirculated air and 1,160 CFM of outside air is cooled to 52°F prior to entering the Control Room envelope
- A centrifugal fan
- 12,500 CFM Centrifugal Fan
- Associated ductwork, instrumentation and controls
What are the power supplies to V‑95/96?
MCC-25
- V-95, Air Handling Unit, ‘A’ Train
MCC-26
- V-96, Air Handling Unit ‘B’ Train
What is the function and power supply for VH-12/13, CRHVC Humidifiers?
- HUC-1683 (HUC-1684) located in MER set at 40% ± 5%.
- Rated 50 lb/hr, required 36 lb/hr
- MCC-79 - VH-13
- MCC-80 - VH-12
- Not required to comply with Technical specifications
What makes up V-26A/B, Emergency Air Filtration Units?
Each Air Filtration Unit consists of the following components:
- Fan V-26A (V-26B)
- Prefilters VFP-26A (VFP-26B)
- Electric Heating Coil VHX-26A (VHX-26B)
- Upstream and downstream HEPA Filters VFH‑26A (VFH-26B)
- Charcoal Filters VFC-26A (VFC-26B)
- Associated ductwork, instrumentation and controls
What is the function of VF-26A/B’s electric heater?
- Electric Resistance Type 15 kW
- Designed to reduce relative humidity of incoming air
- Requires 12.48 kW
- Ensures maximum charcoal filter efficiency
- Power Supply – MCC-25 (MCC-26)
- Minimum air flow for heater operation 2650 CFM
What is the purpose of the charcoal filters within the Emergency Air Filtration Units VF-26A (VF-26B)?
Minimizes exposure to radioactive materials during accident conditions
- Two 2” beds in series (4” total charcoal depth)
- Remove radioactive iodine
What detects fire in the charcoal beds?
Charcoal bed temperature can be monitored at Charcoal Filter Fire Alarm Panel
Dual meter indicates temperature for upstream and downstream charcoal beds.
- Yellow “Detection High Alarm” indicating light illuminates at 220°F.
- Red “Detection High-High Alarm” indicating light illuminates at 280°F.
- Yellow “Detection Abnormal” indicating light illuminates when any of the following occur:
- Open Sensor, terminator, or wiring.
- Faulty or improperly seated status relay on the detection panel
- Malfunction in the detection panel.