CCW Alarms Flashcards

1
Q

Define EK-1155, “WEST ROOM ENG. SAFEGUARD PPS CLG WTR LO FLOW”

A

Sensor: FS-0954 & POS-0879B(SW), POS 0880B(SW) or POS-0913BSetpoint: 9 to 11 gpm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Define EK-1156, “EAST ROOM ENG. SAFEGUARD PPS CLG WTR LO FLOW”

A

Sensor: FS 0958 & POS-0879B(SW), POS-0880B(SW) or POS-0913BSetpoint: 4 to 6 gpm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Define EK-1167, “COMPONENT CLG PUMPS P-52A, P-52B, P-52C TRIP”

A

Sensor: Breaker open with control switch in “After Close” position.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Define EK 1168, COMPONENT CLG PUMPS STNDBY PUMP RUNNING”

A

Sensor: Breaker closed on a pump selected for “Standby.”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Define EK-1169, “COMPONENT CLG PUMPS DISCHARGE LO PRESS”

A

Sensor: PIA-0918, CCW HX E-54A Inlet PressureSetpoint: 80 psigAlternate Indication: E-54B Inlet Pressure

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Define EK-1170/1171, “COMPONENT CLG HX E54A/B HI-LO TEMP”

A

Sensor: TIA 0914/TIA 0916 E-54A/E-54B Outlet TempSetpoint: High: 89º F Low: 71º F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Define EK-1172, “COMPONENT CLG SURGE TANK T-3 HI-LO LEVEL”

A

Sensor: LIA-0917, or LIA-0920Setpoint: High: 93% Low: 35%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Define EK-1365 “PROCESS LIQUID MONITORING HI RADIATION”

A

Sensor: RIA 0915Setpoint: Warning: 6000 CPM Hi: 7000 CPM

How well did you know this?
1
Not at all
2
3
4
5
Perfectly