EK-0755, EK-0756, EK-0757, EK-0758, “PRESSURIZER SAFETY INJ SIGNAL A/B/C/D LO-LO PRESS”
PIA-0102ALL, Pressurizer Lo Press SI Channel - Ckt 1
Trips at 1605 psia
Other Indications
PIA-0102BLL
PIA-0102CLL
PIA-0102DLL
Check other PZR pressure channels, if 2 out of 4, verify SIAS.
EK-1157, “LO PRESS SI PUMPS P-67A & P-67B TRIP”
EK-1157, “LO PRESS SI PUMPS P-67A & P-67B TRIP”
152-206/b, 152-111/b
Breaker open with control switch in AFTER CLOSE position
Check pump indicating lights, check LPSI flow indicators, check LPSI header pressure.
No Automatic Functions
EK-1306, “LO PRESSURE SAFETY INJ MOV OVERLOAD”
EK-1306, “LO PRESSURE SAFETY INJ MOV OVERLOAD”
LOW PRESS SAFETY INJ MOV OVERLOAD
Sensors
- 49-141, 49-147, 49-247, or 49-251
Thermal overload
Check for blue lights on LPSI MOVs.
EK-1312, “HI PRESS SAFETY INJ MOV OVERLOAD”
EK-1312, “HI PRESS SAFETY INJ MOV OVERLOAD”
Sensor
49-137, 49-197, 49-151, 49-157,49-237, 49-241, 49-257, 49-261, 49-2113, 49-2213, 49-2313, or 49-2413
The thermal overload does not interrupt power to the MOV. Due to wiring configurations for the following valve pairs, alarm will not reflash if one MOV of the pair is in alarm and the second MOV of that pair goes into alarm:
- MOV-3068 and MOV-3082;
- MOV-3066 and MOV-3080;
- MOV-3062 and MOV-3081;
- MOV-3064 and MOV-3083.
EK-1313, EK-1319, EK-1325, EK-1331, “SAFETY INJ TANKS T82 A/B/C/D HI-LO LEVEL”
EK-1313, EK-1319, EK-1325, EK-1331, “SAFETY INJ TANKS T82 A/B/C/D HI-LO LEVEL”
- LIA-0365, Safety Injection Tank T-82A Level Alarm
- LIA-0368, Safety Injection Tank T-82B Level Alarm
- LIA-0372, Safety Injection Tank T-82C Level Alarm
- LIA-0374, Safety Injection Tank T-82D Level Sigma
High Level: 48% (Narrow Range)
Low Level: 32% (Narrow Range)
Check level indicators. / Check PPC
EK-1314, EK-1320, EK-1326, EK-1332, “SAFETY INJ TANKS T82 A/B/C/D HI LEVEL”
EK-1314, EK-1320, EK-1326, EK-1332, “SAFETY INJ TANKS T82 A/B/C/D HI LEVEL”
- LS-0340A, Safety Injection Tank T-82A Level Switch
- LS-0360A, Safety Injection Tank T-82B Level Switch
- LS-0348A, Safety Injection Tank T-82C Level Switch
- LS-0375A, Safety Injection Tank T-82D Level Switch
62% (on LIA-0365, Narrow Range)
Alternate Indication
- LIA-0365, Safety Injection Tank T-82A Level Alarm
T.S. 3.5.1 limit 66%
EK-1315, EK-1321, EK-1327, EK-1333, “SAFETY INJ TANKS T82 A/B/C/D LO LEVEL”
EK-1315, EK-1321, EK-1327, EK-1333, “SAFETY INJ TANKS T82 A/B/C/D LO LEVEL”
- LS-0340B, Safety Injection Tank T-82A Level Switch
- LS-0360B, Safety Injection Tank T-82B Level Switch
- LS-0348B, Safety Injection Tank T-82C Level Switch
- LS-0375B, Safety Injection Tank T-82D Level Switch
Trip Setpoints: 18% (on LIA-0365/0368/0372/0374, Narrow Range)
Alternate Indication
- Check Level Indicators
LCO 3.5.1 limit 14%
EK-1316, EK-1322, EK-1328, EK-1334, “SAFETY INJ TANKS T82 A/B/C/D HI-LO PRESS”
EK-1316, EK-1322, EK-1328, EK-1334, “SAFETY INJ TANKS T82 A/B/C/D HI-LO PRESS”
PIA-0363, Safety Injection Tank T-82A Pressure Ind
- PIA-0367, Safety Injection Tank T-82B Press Alarm
- PIA-0371, Safety Injection Tank T-82C Press Alarm
- PIA-0369, Safety Injection Tank T-82D Press Alarm
Trip Setpoints:
- High Pressure: 225 psig
- Low Pressure: 205.5 psig to 208.5 psig
Alternate Indications
PPC indications
EK-1317, EK-1323, EK-1329, EK-1335, “SAFETY INJ TANKS T82 A/B/C/D HI PRESS”
Safety Injection Tk T-82A/B/C/D High Press Switch
Setpoint 225 psig
Alternate Indication
- Safety Injection Tank T-82A/B/C/D Pressure Ind
EK-1318, EK-1324, EK-1330, EK-1336, “SAFETY INJ TANKS T82 A/B/C/D LO PRESS”
EK-1318, EK-1324, EK-1330, EK-1336, “SAFETY INJ TANKS T82 A/B/C/D LO PRESS”
T-82A/B/C/D Low Press Switch
Setpoint: 205 psig
Alternate Indication
- T-82A/B/C/D Pressure Indicators
EK-1340, EK-1341, “SAFETY INJ INITIATION SIGNAL A/B”
EK-1340, EK-1341, “SAFETY INJ INITIATION SIGNAL A/B”
SAFETY INJ INITIATION SIGNAL “A”
- Sensor: SIS-3
- 2/4 Coincidence of less than 1605 psia on PIA-0102ALL, PIA-102BLL, PIA-0102CLL, and PIA-0102DLL,
OR
- 2/4 Coincidence of greater than 3.7 psi to 4.4 psi on PS-1801, PS-1802A, PS-1803, and PS-1804A,
OR
- Safety Injection Test Switch TS/PB-L
SAFETY INJ INITIATION SIGNAL “B”
- Sensor SIS-4
- 1605 psia on PIA-0102ALL, PIA-102BLL, PIA-0102CLL, and PIA-0102DLL,
OR
- 2/4 Coincidence of greater than 3.7 psi to 4.4 psi on PS-1801A, PS-1802, PS-1803A, and PS-1804,
OR
- Safety Injection Test Switch TS/PB-L
Alternate Indications
- Check PCS Pressure and Containment Pressure
EK-1342, “SAFETY INJ INITIATED”
EK-1342, “SAFETY INJ INITIATED”
Sensor:
- SIS-1 and SIS-6
Trip Setpoints:
- Coincident closure of contacts
Alternate Indication:
- None
- Check ALL SIAS Equipment Operating
EK-1352, EK-1353, “EAST/WEST SFGRDS ROOM SUMP HI/PANEL UV”
EK-1352, EK-1353, “EAST/WEST SFGRDS ROOM SUMP HI/PANEL UV”
Sensor:
- LS-1108, Eng Safeguard Room Sump Pump Start/Stop
Trip Setpoints:
- Approx 34 inches from bottom or 14.2% on LI-1110A (sump is 66 inches deep)
- Loss of power to sump alternator relay panel (EY-01, Instrument AC Panel, Breaker 35)
AlternateIndication:
- East Engineered Safeguards Sump level indication
EK-1355, EK-1356, “SIRW TANK T-58 HI-LO LEVEL”
EK-1355, EK-1356, “SIRW TANK T-58 HI-LO LEVEL”
Sensor:
- LIA-0331, SIRW Tank Level Indication Alarm
Trip Setpoints:
- High Level: 285 inches or 99%
- Low Level: 261 inches or 90%
Alternate Indication:
- LIA-0332A T-58 level
Technical Specifications LCO 3.5.4 (85% equals 250,000 usable gallons) actions.
EK-1357, “SIRW TANK T-58 ½ TAKEN TWICE LO LEVEL”
EK-1357, “SIRW TANK T-58 ½ TAKEN TWICE LO LEVEL”
Sensor:
- Relays 4L3 or 4L4
Trip Setpoints:
- 24 inches (2% on LIA-0331 or LIA-0332A)
Alternate Indication:
- None