Main Turbine Control and Supervisory Alarms Flashcards
EK-0101, “TURBINE TRIP”
EK-0101, “TURBINE TRIP”
Sensor:
- 63/AST-1, Auto Stop Trip Pressure Switch 74/AST,
Trip Setpoints:
- 45 psi Auto Stop Oil Pressure and Oil Dump Solenoid operated
Alternate Indication:
- Main Stop, Governor, Reheat Stop, and Combined Intercept Valves CLOSED
Reactor Trip if greater than 15% Reactor Power.
Main Stop, Governor, Reheat Stop, and Combined Intercept Valves close.
Cooling Tower Fans trip.
Atmospheric Dump Valves and/or Turbine Bypass Valve open per program.
Feedwater flow controllers FIC-0701 and FIC-0703 transfer to MANUAL, and Feedwater Pump(s) ramp down to 5% flow.
EK-0102, “TURBINE OVERSPEED TRIP”
EK-0102, “TURBINE OVERSPEED TRIP”
Sensor:
- OS 63/AST-1, Auto Stop Trip Pressure Switch
Trip Setpoints:
- 1940 to 2020 RPD, and 45 psi Auto Stop Oil Pressure
Alternate Indication:
- Main Stop, Governor, Reheat Stop, and Combined Intercept Valves CLOSED
The alarm is actuated by 63/AST-1, automatic functions are initiated by a two out of three logic actuation between 63/AST-1, 63/AST-2, and 63/AST-3.
- Reactor Trip if greater than 15% Reactor Power.
- Main Stop, Governor, Reheat Stop, and Combined Intercept Valves close.
- Cooling Tower Fans trip.
- Atmospheric Dump Valves and/or Turbine Bypass Valve open per program.
- Feedwater flow controllers FIC-0701 and FIC-0703 transfer to MANUAL, and Feedwater Pump(s) ramp down to 5% flow.
EK-0103, “TURBINE ROTOR ECCENTRICITY”
EK-0103, “TURBINE ROTOR ECCENTRICITY”
Sensor:
- VIA-0525, Rotor Eccentricity Monitor
Trip Setpoints:
- 9 mil eccentricity
Alternate Indication:
- None
OBSERVE trend on TUR-0520 (PT37), Turbine Vibration Eccentricity and Expansion Recorder.
Leave Turbine on Turning Gear until eccentricity less than 9 mil.
EK-0104, “TURBINE DIFF EXPANSION ROTOR LONG/SHORT”
EK-0104, “TURBINE DIFF EXPANSION ROTOR LONG/SHORT”
Sensor:
- POIA-0527, Differential Expansion Monitor (Generator End),
or
- POIA-0528, Differential Expansion Monitor (Governor End)
Trip Setpoints:
- GENERATOR END:
- Rotor Long, 330 mils
- Rotor Short, 700 mils
- GOVERNOR END:
- Rotor Long, 200 mils
- Rotor Short, 700 mils
Alternate Indication:
None
EK-0105, “TURBINE HI VIBRATION”
EK-0105, “TURBINE HI VIBRATION”
Sensor:
- TUR-0520, Turbine /Generator/MSR Condition Monitor
Trip Setpoints:
- 7 mils
Alternate Indication:
- Turbine Supervisory Instrument Panel
Vibration alarms on TUR-0520 actuate on absolute value (combination of relative and seismic). EC-23A relative (REL) valves use proximity probes which may indicate lower than absolute.
CAUTION
If Turbine vibration due to water induction, then do not trip Turbine until 14 mils vibration is exceeded. Damage can occur due to rubs as the Turbine coasts down through its critical speeds. Damage can also occur due to stator warping after coming to rest due to differential cooling of the Turbine Casing.
EK-0106, “EXHAUST HOOD HI TEMP 217º F”
EK-0106, “EXHAUST HOOD HI TEMP 217º F”
Sensor:
- TS-0536, Exhaust Hood Spray to LP Turbine Temp
- TS-0544, Low Pressure Turbine B High Temp Switch
Trip Setpoints:
- 217F
Alternate Indication:
- TI-0594, #1 LP Exhaust Hood (Turbine)
- TI-0595, #2 LP Exhaust Hood (Turbine)
If Main Generator is online, then raising load should lower Exhaust Hood temperature.
EK-0107, “TURBINE NO LOAD PRETRIP”
EK-0107, “TURBINE NO LOAD PRETRIP”
Sensor:
- 452-X, Auxiliary Relay-Interlock Generator ACB
- 63D-X/AM, Turbine Prot Differential Pressure Switch
Trip Setpoints:
- With Generator Breakers 25H9 or 25F7 and MOD 26H5 CLOSED, 8 psid lowering across High Pressure Turbine first stage.
Alternate Indication:
- None
Turbine will trip if condition persists for 60 seconds.
EK-0108, “BEARING OIL PRESS PRETRIP”
EK-0108, “BEARING OIL PRESS PRETRIP”
Sensor:
- 63/LBO, Main Turbine K-1 Bearing Oil Low
Trip Setpoints:
- 8 psig lowering
Alternate Indication:
- Turning Gear Oil Pump
P-26, Turning Gear Oil Pump, auto start at 9 psig.
P-27, Turbine Gen K-1 Emergency Bearing Oil Pp, auto start at 6 psig.
Turbine Trip at 5 to 7 psig.
EK-0109, “THRUST BEARING PRETRIP”
EK-0109, “THRUST BEARING PRETRIP”
Sensor:
- POIAX-0525, Turbine Thrust Position Monitor Aux Relay
Trip Setpoints:
- 35 mils Turbine Shaft axial movement in either direction
Alternate Indication:
- None
(Turbine will trip at 40 mils in either direction)
REDUCE Turbine load at maximum permissible rate per GOP-8.
EK-0110, “VACUUM PRETRIP”
EK-0110, “VACUUM PRETRIP”
Sensor:
- 63/LV, Main Turbine K-1 Low Vacuum Pretrip
Trip Setpoints:
- 21.5 inches Hg decreasing
Alternate Indication:
- Turbine Backpressure
Turbine will trip at 18 inches Hg to 21 inches Hg
EK-0111, “VACUUM LO”
EK-0111, “VACUUM LO”
Sensor:
- PS-0761, Condenser Low Vacuum
Trip Setpoints:
- 24 inches Hg
Alternate Indication:
- Turbine Backpressure
Turbine will trip at 18 inches Hg to 21 inches Hg.
PT_0763 (PPC) alarms at 6 inches Hg Turbine Backpressure
EK-0113, “EH SYSTEM LO-LO LEVEL TRIP”
EK-0113, “EH SYSTEM LO-LO LEVEL TRIP”
Sensor:
- 386/LFT, Turbine Prot-Lockout EH Sys on Lo Oil Lv
Trip Setpoints:
- 7-5/8 inches from bottom of EH Reservoir
Alternate Indication:
- Local EHC level
EH Pump selected for AUTO START:
- Will lock out if not running.
- Will not trip if running.
EK-0114, “EH FLUID HI-LO LEVEL”
EK-0114, “EH FLUID HI-LO LEVEL”
Sensor:
- 71/FL-1, EHC Reservoir Hi/Lo Level Alarm
Trip Setpoints:
- High: 21 5/8 inches from bottom of reservoir.
- Low: 11 5/8 inches from bottom of reservoir.
Alternate Indication:
- Local EHC level
EK-0115, “EH SYSTEM HI TEMP/PRESS”
EK-0115, “EH SYSTEM HI TEMP/PRESS”
Sensor:
- 63/HP, EH Fluid Pressure High Pressure Switch
- 26/HFT, EHC High Fluid Temperature Switch
Trip Setpoints:
- 2200 psig
- 135F
Alternate Indication:
- Local EHC temperature
- Local EHC fluid pressure
EK-0117, “TURBINE-GEN BEARING HI TEMP”
EK-0117, “TURBINE-GEN BEARING HI TEMP”
Sensor:
- TUR-0520/TSI
Trip Setpoints:
- 210F
Alternate Indication:
- Local bearing temperature indicators
IF one or more bearing temperatures exceed 225F, THEN REMOVE unit from service per GOP-8.
EK-0118, “TURB-GEN LUBE OIL HI TEMP”
EK-0118, “TURB-GEN LUBE OIL HI TEMP”
Sensor: TUR-0521 ALM 01
Trip Setpoints: 50C
Alternate Indication:
TI-1401, Lube Oil Cooler Outlet Local Indicator
CHECK TUR-0521, Generator/Transformer/Lo Temperature & Thr Brg Pos/Speed, Point 07 to determine temperature and rate of temperature change.
EK-0119, “EH SYSTEM BACKUP PUMPS P19A & P19B AUTO START”
EK-0119, “EH SYSTEM BACKUP PUMPS P19A & P19B AUTO START”
Sensor:
- 42-357A/42-437A
Trip Setpoints:
- Control switch in AUTO START position and1750 psig system pressure
Alternate Indication:
- None
IF EH pressure remains low AND is due to system leakage, THEN REMOVE unit from service per GOP-8.
EK-0120, “EH PUMP P19A AND/OR P19B OUT OF SERV”
EK-0120, “EH PUMP P19A AND/OR P19B OUT OF SERV”
Sensor: 74-357 74-437
Trip Setpoints:
Control switch in PULL-TO-LOCK position
Alternate Indication:
None
EK-0123, “TURB PROT & BLEEDER TRIP CKTS UNDERVOLTAGE”
EK-0123, “TURB PROT & BLEEDER TRIP CKTS UNDERVOLTAGE”
Sensor:
- 374/U1,
- 374/U2,
- 374/U3, or
- 374/U4
Trip Setpoints:
- Loss of potential
Alternate Indication:
- None
CHECK CV-0510, S/G E-50A MSIV (MZ-2), and CV-0501, S/G E-50B MSIV (MZ-3), position indication lights on EC-01, Turbine Generator Control Console, illuminated.
IF loss of DC Panel(s) D11-1, D21-1 or D21-2 is indicated, THEN REFER TO AOP-17.
EK-0124, “GLAND SEAL CONDENSER E-19 LO VACUUM”
EK-0124, “GLAND SEAL CONDENSER E-19 LO VACUUM”
Sensor:
- PS-0632, Gland Seal Condenser E-19
Trip Setpoints:
- 10 inches H2O
Alternate Indication:
- None
CHECK at least one Condensate Pump P-2A or P-2B operating.
CHECK C-1A or C-1B, Gland Steam Condenser Exhauster, operating.
IF necessary, THEN SHIFT Exhausters per SOP-13.
EK-0125, “TURBINE –GEN OIL PUMPS P-26, P-27 AUTO START”
EK-0125, “TURBINE –GEN OIL PUMPS P-26, P-27 AUTO START”
Sensor:
- 42-277A / 42-117A
Trip Setpoints:
- P-26, Turning Gear Oil Pump: 9 psig
- P-27, Turbine Gen K-1 Emergency Bearing Oil Pp: 6 psig
Alternate Indication:
- None
Condition is normal after Main Turbine is tripped.
EK-0126, “EMERG BRG OIL PUMP P-27 OUT OF SERVICE OVERLOAD”
EK-0126, “EMERG BRG OIL PUMP P-27 OUT OF SERVICE OVERLOAD”
Sensor:
- 74-117 / 49-117
Trip Setpoints:
- Control switch in PULL-TO-LOCK position
OR
- Thermal overload (alarm only)
OR
- 52-117, Emergency T/G Bearing Oil Pump P-27, OPEN
Alternate Indication:
- None
P-27, Turbine Gen K-1 Emergency Bearing Oil Pp, auto start is blocked.
IF unit was on Turning Gear and P-26, Turning Gear Oil Pump, is NOT in service, THEN VERIFY unit Turning Gear Drive Motor has stopped.
IF control switch is NOT in PULL-TO-LOCK position, THEN: STOP P-27; DETERMINE cause of thermal overload.
EK-0127, “TURNING GEAR OIL PUMP P-26 OUT OF SERV/OVERLOAD”
EK-0127, “TURNING GEAR OIL PUMP P-26 OUT OF SERV/OVERLOAD”
Sensor:
- 74-277 49-277
Trip Setpoints:
- Control switch in PULL-TO-LOCKposition
OR
- Thermal overload (alarm only)
Alternate Indication:
- None
P-26, Turning Gear Oil Pump, auto start is blocked.
OPERATOR ACTION:
IF unit was on Turning Gear and P-27, Turbine Gen K-1 Emergency Bearing Oil Pp, is NOT in service, THEN VERIFY Turning Gear Drive Motor has stopped.
IF control switch is NOT in PULL-TO-LOCK position, THEN: STOP P-26.
DETERMINE cause of thermal overload.
EK-0128, “TURBINE SHAFT ZERO SPEED”
EK-0128, “TURBINE SHAFT ZERO SPEED”
Sensor: 62/ZSX
Trip Setpoints: 0 RPM
Alternate Indication:
None
Alarm indicates K-2, Main Turbine Turning Gear, has either tripped or has not automatically engaged.
NOTE: The stop pushbutton on Panel EC-277 will stop Turning Gear regardless of Panel EC-01 control switch position.
EK-0131, “TURBINE L.O. RES VAPOR EXT C5 TRIP”
EK-0131, “TURBINE L.O. RES VAPOR EXT C5 TRIP”
Sensor:
- 42-351, L.O. Reservoir Vapor Extractor C-5A Starter
- 42-553, L.O. Reservoir Vapor Extractor C-5B Starter
Trip Setpoints:
- Either breaker B contact with associated control switch in AFTER START position.
Alternate Indication:
- Control Room running lights
EK-0134, “TURBINE/GEN LIFT PUMP LOW DISCHARGE PRESSURE”
EK-0134, “TURBINE/GEN LIFT PUMP LOW DISCHARGE PRESSURE”
Sensor:
- AR/BL
Trip Setpoints:
- 600 psig with control switch in AUTO START or RUN positions.
Alternate Indication:
- Local bearing oil lift discharge pressure
Alarm is bypassed when Main Turbine speed is greater than 600 rpm.
OPERATOR
EK-0135, “TURBINE/GEN LIFT PUMP TROUBLE
EK-0135, “TURBINE/GEN LIFT PUMP TROUBLE
Sensor:
- B3, B4, B5, B6, D3, D4, D5, D6
Trip Setpoints:
- Low Suction Pressure (less than or equal to 1 psig) or Suction Filter high d/p with control switch in AUTO SWITCH or RUN positions.
Alternate Indication:
- EC-277, Turning Gear Console, to determine affected Turbine Bearing Oil Lift Pump
EK-0318, “TURBINE PANEL TROUBLE”
EK-0318, “TURBINE PANEL TROUBLE”
Sensor:
- DEH CRT
Trip Setpoints:
- Priority 3 Alarms
- (see Attachment 1, “DEH Priority 3 Alarms”)
Alternate Indication:
- None
CALL UP alarm subscreen.
• PUSH Silence Key to enable reflash of alarm window.
• REFER TO Attachment 1.
EK-0320, “MAIN SEAL OIL PUMP P22 TRIP”
EK-0320, “MAIN SEAL OIL PUMP P22 TRIP”
Sensor:
- ‘b’ contact in associated breaker Trip
Setpoints:
- Breaker tripped with associated handswitch in AFTER CLOSE position
Alternate Indication:
- None
VERIFY PCV-SO1430, Seal Oil Turbine Backup PCV, from main lube oil maintaining Seal Oil pressure approximately 10 psid on:
DPIT-1491, Exciter End Seal Oil Diff Pressure
DPIT-1492, Turbine End Seal Oil Diff Pressure
IF necessary, THEN START OR VERIFY STARTED P-24, High Pressure Seal Oil Pump.
IF PCV-SO1430, Seal Oil Turbine Backup PCV does NOT maintain Seal Oil pressure, THEN START OR
VERIFY STARTED P-23, Backup Seal Oil Pump.
EK-0321, “SEAL OIL BACKUP PUMP P-23, P-24 AUTO START”
EK-0321, “SEAL OIL BACKUP PUMP P-23, P-24 AUTO START”
Sensor:
- P-23, Backup Seal Oil Pump: DPS-1490
- P-24, High Pressure Seal Oil Pump: 63/TGP-2
Trip Setpoints:
- P-23: 5 psid
- P-24: 9 + 2 psig
Alternate Indication:
- None
EK-0322, “SEAL OIL BACKUP P-23 OUT OF SERV OVERLOAD”
EK-0322, “SEAL OIL BACKUP P-23 OUT OF SERV OVERLOAD”
Sensor: 74-299 49-299
Trip Setpoints:
Undervoltage or Thermal Overload (alarm only)
Alternate Indication:
None
EK-0324, “GENERATOR LO VAPOR EXTRACTOR C7 TRIP”
EK-0324, “GENERATOR LO VAPOR EXTRACTOR C7 TRIP”
Sensor: ‘b’ contact in breaker Trip
Setpoints: Breaker tripped with Handswitch in AFTER CLOSE position
Alternate Indication: None
WARNING
Vapors escaping past Generator Bearing Seals
while Extractor C-7 is out of service will contain
Hydrogen.