Pressurizer Level Control Flashcards
What is the purpose of the Pressurizer Level Control System
- Provides sufficient water volume to prevent draining the Pressurizer as a result of a reactor trip yet minimizes the water volume to reduce the energy release and resultant containment pressure rise during a Loss of Coolant Accident.
- Method of maintaining the proper water volume is to control the level to a calculated setpoint that is programmed as a function of average primary coolant temperature.
What are the inputs to the Pressurizer Level Control system?
- Pressurizer level Hot Calibrated Control Channels, (LT-0101A/B) for actual Pressurizer level
- Tavg signal via TYT-100 (loop 1) or TYT-200 for program Pressurizer level based on PCS temperature which is related to reactor power.
What is the pressurizer level control program output?
Controllers establish a Pressurizer level setpoint proportional to Tave.
Normal and Backup signals are then sent to control:
- P-55A speed
- P-55B/C Start and Stop
- CV-2004/2005 Open and Close
What are the modes of operation for the level controlers?
Cascade
- Allows internally generated Pressurizer level setpoint to be controlling signal.
Auto
- Allows operator to generate Pressurizer level setpoint.
- Band must be within confines of Backup Level Control Program
Manual
- Allows operator to control output signal of controller.
- Band must be within confines of Backup Level Control Program
How is pressurizer level calculated?
Internal programming of LIC-0101A and LIC-0101B calculated it.
- Ramps linearly from 42% Pressurizer level at 0% power to 57% Pressurizer level at 100% power.
- 532ºF equates to 0% power = 42% level
- 560ºF equates to 100% power = 57% level
Describe normal pressurizer level control.
Only Outputs in Cascade mode of operation.
Controller generates an output signal due to a deviation from the calculated setpoint. Controller will continue to raise or lower the output signal based on the amount of deviation from setpoint.
Higher the output signal (vs 50%) - less charging more letdown (signal indicator in output meter moving toward the right).
50% output signal (0 deviation) P-55A at required capacity CV-2003 is Open
What actions occur as level rises from setpoint and deviation from setpoint grows larger?
50% output signal start
- P-55A at required capacity and CV-2003 is Open
69. 3% output signal - Open CV-2004
72. 4% output signal - Min Speed P-55A
88. 5% output signal - Open CV-2005
What actions occur as level lowers from setpoint and deviation from setpoint grows larger?
50% output signal start
- P-55A at required capacity and CV-2003 is Open
30. 8% output signal - Start P-55B
27. 6% output signal - P-55A at Max Speed
24. 3% output signal - Start P-55C
What is the full sequence on rising level from minimum controler output to max?
- Max Speed P-55A
- Trip P-55C
- Trip P-55B
- P-55A at Required Speed and CV-2003 open (zero deviation: 50% output)
- Open CV-2004
- P-55A at Minimum Speed
- Open CV-2005
What is the full sequence on lowering level from maximum controler output to min?
- Minimum Speed P-55A
- Close CV-2005
- Close CV-2004
- P-55A at Required Speed and CV-2003 open (zero deviation: 50% output)
- Start P-55B
- P-55A at maximum speed
- Start P-55C
What is Backup Level Control?
Backup signals from Controller are separate ON/OFF signals independent of normal output signals.
Backup signal overrides the normal output signal.
Generated within the controller, actions occur based on deviation of Pressurizer level from the internally calculated setpoint as determined by selected Tave signal.
(P-55A has no input from the backup level control)
What actions are associated with a +6% deviation via the Backup Level Control?
Hi-Lo Level Alarm (EK-0761)
What actions are associated with a +5% deviation via the Backup Level Control?
- Backup Heaters On (Already On)
- Open CV-2004 and CV-2005
- Trip P-55B and P-55C
What actions are associated with a +4% deviation via the Backup Level Control?
- Hi-Lo Level Alarm Off (EK-0761)
What actions are associated with a +2% deviation via the Backup Level Control?
- Backup Heater Off
- Permit P-55B and P-55C Start
- Permit CV-2004 and CV-2005 Closure
What actions are associated with a -4% deviation via the Backup Level Control?
- Hi-Lo Level Alarm Off (EK-0761)
- Permit P-55B & P-55C Stop
- Permit CV-2004 & CV-2005 Open
What actions are associated with a -2% deviation via the Backup Level Control?
- Hi-Lo Level Alarm On (EK-0761)
- Start P-55B & P-55C
- Close CV-2004 & CV-2005