SQ- Radiation Monitoring Flashcards

1
Q

[SQ]
3 subsystems?
Where is the data sent to?

A

SRMS / PAMS / DRMS

Safety Related / Post-Accident / Digital Radiation

Display/ Controls: Main CR and RMS/Effluents Office

Data sent to ERFDADS

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

[SQ]
PAMS purpose?

A
  • Condenser effluent and Plant vent
  • Post Accident & Long term monitoring of effluent gases and particulates.
  • It informs operators of abnormal radiation in:

containment penetration areas,
main steam line area,
control room and other plant areas

(some are tech spec related)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

[SQ]
DRMS purpose?

A

BOP radiation monitoring system
-Info on process, effluent, and area radiation levels

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What types of monitors are used in each of the SQ subsystems?

A

Quality class QAG monitors

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

[SQ]
What does SRMS provide? What types of monitors does it use?

A

ESF Actuation signals

technical specification monitoring and control functions

Contains only quality class Q radiation monitors

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

[SQ]
Auto Features associated with RU-1?

A

CTMT Atmosphere Monitor

CIAS - CIVs auto shut to isolate the RU monitor from pressure and temperature transients following a LOCA.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

[SQ]
RU-29 and RU-30 Location?
Auto Features?

A

CR Vent Intake Monitor

  • Track noble gas concentrations in the control room air intake.
  • HI-Hi Alarm
  • CREFAS - activating the CR essential filtration units.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

[SQ]
Auto Features RU-145?

A

PAMS low range monitor

Hi-Hi Alarm
- FEBEVAS (Isolates Normal FB Vent, Starts Essential Ventilation)
- Cross Trips CREFAS

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

[SQ]
FB Ventilation Exhaust RU Monitor?
FB Actuation Signals?

A
  • 145
  • FEBEVAS & CREFAS
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

[SQ]
RU-37 and RU-38 location?
Auto Features?

A

[CH] Power Access Purge Monitors
O/S CTMT
- between the power access purge exhaust and refueling purge exhaust ducts

-ESF actuation
high-high alarm CPIAS. This signal cross trips with CREFAS

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

[SQ] RU-31?

A

FB Fuel Pool

Hi-Hi (Isolates FB Normal Ventilation, Starts FB Essential)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

[SQ] RU-141 Auto Features?

A

Gland Seal

Monitors for gaseous activity resulting from a primary to secondary leak.

RU-141 is a two channel (141A and 141B) beta scintillation detector.

Channel 141A measures the combined air removal and gland steam flow,

Channel 141B being mounted on the discharge piping of the air removal pumps only.

A high alarm on RU-141A will initiate the operation of the air removal system post filter system.

RU-141B provides alarm function only

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

In the SQ system, what is the automatic feature associated with Aux. Steam Condensate Receiver Tank Inlet Monitor, RU-7?

A

Auxiliary steam condensate returning from the boric acid concentrator, LRS evaporator and gas stripper is monitored before it leaves the receiver tank.

High activity alarm is indicative of radioactive leakage into one or more of the process components or improper operation.

Upon high-high alarm the RTI monitor automatically diverts the condensate to the liquid radwaste system

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

In the SQ system, what is the automatic feature associated with Waste Gas Decay Tank Monitor, RU-12?

A

to monitor the gross beta radioactivity level in the decay tank discharge header

A high activity alarm provides an indication of an abnormal operating condition, such as, an inadvertent discharge or incorrect valve lineup.

The monitor high-high activity alarm initiates isolation of the decay tank discharge header

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

How often are the non-tech spec SQ monitors calibrated? What about for the tech. spec ones?

A

At least every 18 months or following corrective maintenance

weekly, monthly, quarterly are required depending on the montior

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What happens on a loss of the T/S related [SQ] monitors? Offsite Dose Calculation Manual related ones?

A

-T/S action must be taken to fix the problem

-compensatory actions must be taken, such as sampling