[ED] - Extraction Steam and Drains Flashcards
[ED]
[ED] purpose?
Extraction Steam & Drains
Preheats CD and FW prior to feedwater entering the S/Gs to increase plant efficiency
[ED]
What provides steam to #4 LP feedwater heater during startup?
Extraction Steam & Drains
[AS]
[ED]
What water system makes-up to the bottom of the ED blowdown stack?
Extraction Steam & Drains
[DS] Domestic Water
[ED]
What is the purpose of the ED blowdown stack?
Extraction Steam & Drains
-collection point for steam traps, HP heater relief valves and miscellaneous [AS] header drains
Aux Steam
[ED]
When is [DS] added to [ED] blowdown stack?
What occurs if [DS] is OOS?
(Domestic Water)
Extraction Steam & Drains
If temp of water >150F
Steam will come out of the blowdown stack and north Condenser sump
[ED]
GA-N2 & ED?
Extraction Steam & Drains
Supplies Nitrogen blanketing of FW Heater Shells & HDTs during long term shutdown operations
Feedwater
Heater Drain Tanks
[ED]
[IA] & [ED]?
2
Extraction Steam & Drains
[MT] control system uses [IA] in Turbine Critical and Non-Critical Relay Dump Valves (provide a signal to control BTVs)
For use all [ED] AOVs
Main Turbine
Bleeder Trip Valves
Instrument Air
Air Operated Valves
Extraction Steam & Drains
[ED]
How are BTV’s affected by a loss of [IA]?
Extraction Steam & Drains
Bleeder Trip Valves
go partially closed (Lose open permissives)
remain open due to [ED] flow
Bleeder Trip Valves
Extraction Steam
Where are the Heater Drain Pumps powered from?
Extraction Steam & Drains
‘A’ from NBN-S02
‘B’ from NBN-S01
[ED]
Where does seal water for each Heater Drain Pump come from?
Extraction Steam & Drains
Condensate Header
(375-500 psig)
[ED]
What positions the Heater Drain Pump mini-flow valves? When will it close? What controls the position of the heater drain pump discharge valve?
Extraction Steam & Drains
Heater Drain Pumps flow transmitter
as the unit comes up in power and more extraction drain flow is available
heater drain tank normal level control valve
[ED]
What signals stop the Heater Drain Pumps?
3
Extraction Steam & Drains
HDT lo-lo level alarm
Heater Drain Pump low flow after a time delay
Electrical protection signal
[ED]
Where are Heater Drain Pumps located?
What allows one heater drain pump operation?
Extraction Steam & Drains
TB 100’ (West of Main Feed Pumps)
Open suction
and vent cross-tie between HDTs
Heater Drain Tanks
[ED]
Why doesn’t #5 FW Heater have a level control system?
Extraction Steam & Drains
No drain cooler region
Drains directly to the HDT
Heater Drain Tank
[ED]
Which LP FW heaters have four inlets?
How many do the others have?
Extraction Steam & Drains
1 & 2
3 & 4 have 1 inlet each
Which feedwater heater has an input from S/G blowdown system?
Extraction Steam & Drains
3
[ED]
What is the purpose of the BTVs? Which feedwater heaters have BTVs?
Extraction Steam & Drains
Bleeder Trip Valves
Prevent [MT] reverse steam flow (overspeed) on Turbine Trip
3-7
Main Turbine
[ED]
What on the BTVs assists disc opening with min differential steam pressure?
Extraction Steam & Drains
Bleeder Trip Valves
Balance Arm device
What happens the Bleeder Trip Valve test valve actuates?
Extraction Steam & Drains
air pressure across the operator piston is equalized to allow partial closing of valve disc by spring force
Why are there 2 BTVs on #4 FW heater extraction line?
Extraction Steam & Drains
Feedwater
there is enough energy in #4 by itself to cause an overspeed trip
[ED]
Which level control valves are reverse acting in [ED]?
Extraction Steam & Drains
All high level CVs and #1 LP heater normal level CVs
Low Pressure
Control Valves
At what air signals are the reverse acting valves full open and full closed in the ED system?
Extraction Steam & Drains
Full open with 3#
Full closed with 15#
(Direct acting is the complete opposite)