CE- Stator Cooling Water / Isophase Bus Duct Cooling Flashcards
What is the purpose of the Stator and Isophase cooling water systems?
To provide cooling for the main generator stator windings, generator bushings, the rectifier excitation system and the generator lower frame extension
Isophase bus cooling provides cooling for the electrical buses from the main generator terminals to the main power transformer and the Unit Aux Transformer
What is the cooling medium for the stator cooling water heat exchangers?
Turbine cooling
What system supplies makeup water to stator cooling system?
Demineralized Water
What system provides cooling to the collector housing heat exchanger?
Normal Chilled Water
What is the capacity of the Stator Cooling Water pumps? Power source? Location?
100% capacity pumps each 1000gpm, one running, one standby
NG
140’ turbine building, north east corner
What would cause the standby Stator Cooling Water Pump to auto start?
In-service pump’s discharge pressure decreases below its low discharge set point
What is the capacity of each Stator cooling cooler? What flows through the tubes of the cooler?
80% capacity
Turbine Cooling water
What is the purpose of the Stator Cooling Coolant Tank? Location? Capacity?
NPSH to pumps and surge volume
140’ Turbine Building, northeast corner
1070 gallons
What is the purpose of the stator cooling test valve? Where are the two test pushbuttons for the auto start of the CE standby pump and how do they work? Where is the valve located?
allows testing of the automatic sequence for the standby pump
Locally and in the Control Room
It simulates low pressure in the discharge line by opening a port to the storage tank
140’ turbine building below the stator cooling water storage tank
While the plant is operating, the in-service discharge pressure drops low enough to start the CE standby pump. Pressure is returned to normal. What is the status of the standby pump?
Still running, it will need to be secured manually
Unless there’s a turbine trip of course
What pressure is the stator cooling water being supplied to the main generator maintained at? In what position is the associated PCV locked?
60 psig
throttled
What temperature is stator cooling water maintained at prior to entering the generator inlet?
42C
How does the 3-way temperature control valve, TV-33, fail upon a loss of air?
Fails to the full cooling position
What is the cooling medium for the Isophase Bus Cooling Coils? What adjusts cooling flow rate? Location?
Turbine Cooling Water
cooler outlet valves
140’ turbine building
What is the capacity of the Isophase Cooling Air Blowers? What powers these blowers? Location?
100% capacity, both still operate at the same time however
NG
140’ turbine building