What are the functions of the MT system?

3

A

thermal energy (SG) in mehanical energy to drive the Main generator

extraction steam for FW (plant efficiency)

hot reheat steam for MFWPT

Main Feedwater Pump Turbines
Feedwater

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

[MT]

Which valves in [MT] are provided with [CO]?

3

Main Turbine
Control Oil

A

Main Turbine Stop Valves (SV)

Control Valves (CV)

Combined Intercept Valves (CIV)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

[MT]

What is the purpose of the Electro-Hydraulic Control (MT-EHC)?

A

-Governs speed, acceleration, load, loading rate, and steam flow to MT during all operations.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

[MT]

What provides hood spray cooling for LP turbine shell exhaust during turbine startup?

A

[CD]
Condensate System

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

[MT]

The turbine consists of what 2 components?

A

Rotor Assembly

Turbine Shell

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Where is steam injected into the HP turbine?

A

Center
where steam expands axially in both directions

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

[MT]

How many stages in the HP turbine?

A

7

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

The turbine shell is designed to withstand what temperature and pressure?

A

Temperature changes in excess of 200F

Pressure drop of 700 psi

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

LP turbine and HP turbine are similar in design, with what exceptions in regards to the LP turbine?

A

Wheels in the latter stages of the low pressure unit are larger than those in the high pressure unit to facilitate maximum energy transfer of low quality steam

Stellite erosion shields are located on the back of the leading edge of the vanes to minimize the affects of water droplet impingement

Grooves are cut in the back of the vanes to aid in the removal of water accumulation

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What are the three primary functions of the LP turbine exhaust hood?

A

Serves as a transition structure between the last stage exhaust and the condenser

Serves as the supporting structure for the rotor bearings

Sustains various external forces imposed upon it

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Main Turbine Exhaust hoods are designed on the assumption that operating temperatures will not exceed what temperature? Effects if exceeded? How do we alleviate such deviations?

A

300F

Harmful distortions could occur resulting in clearance deviations

Water spray manifolds are installed downstream of the last stage buckets, out of the normal steam path

(This spray may be initiated automatically on high exhaust hood temperature or manually by operating a bypass valve)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What is used to prevent the main turbine exhaust hood operating with a positive pressure when a loss of CW occurs?

A

Three Atmosphere Relief Diaphragms (Rupture Disks) mounted on top of each LP turbine shell

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What is the purpose of the Main Turbine Thrust Bearing? Where is the thrust bearing located?

A

Absorbs axial thrust of the turbine and generator rotors, which are connected by a solid coupling

between the HP turbine and first LP turbine

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

How many journal bearings are on the main turbine rotor and where are they located? How are they cooled?

A

two, one at each end of the turbine section (one at each end of the main generator)

oil

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What is the purpose of the Main Turbine Turning Gear?

A

To rotate the shaft slowly and continuously during shutdown periods when rotor temperature changes occur

jack rotor small amounts for inspections

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What would be the adverse effect of leaving the main turbine shaft stationary during cooldown periods?

A

Shaft distortion

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

When starting the Turning Gear, what interlocks must be met before the piggyback motor will start?

A

The main generator circuit breakers or motor operated disconnect are/is open

A bearing lift pump is running

Bearing lube oil pressure is adequate

Turning Gear is disengaged

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

Once the piggyback motor is started, when will the turning gear engage?

A

If rotor speed is less than 2 rpm and if a low speed permissive signal is generated by the EHC

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

Main Turbine steam admission valve Control PACs consist of what components?

A

Hydraulic cylinder, which operates on oil from the 1600 psig control oil system

Disk dump valve assembly that mounts on the bottom of the hydraulic cylinder

Various servo-valves, solenoid valves, and pressure controlled shutoff valves mounted to the lower end cap block “B” of the hydraulic cylinder

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

What are the two general types of control PACs?

A

One for controlling steam valve

One for non-controlling steam valve

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

Where are the Main Turbine Stop Valves located?

A

150’ level of the Turbine Building

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
22
Q

The bypass valve provided in main turbine Safety Valve #2 is capable of passing steam to permit what?

A

Slow warming of the stop valve below seat areas and control valve bodies

Pressurizing the stop valve below seat areas necessary for opening the SVs

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
23
Q

What happens is if a single main turbine Control Valve fails open during a Turbine Trip?

A

All SVs would need to close to isolate main steam from the turbine because the steam chest located below the SVs cross connects all the CV inlets

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
24
Q

What is the purpose of the Main Turbine Control Valves?

A

To control main steam flow into the high pressure turbine during startup and shutdown

regulate steam flow to suit load requirements during normal operation

serve as the first line of defense to prevent excessive over speeding during emergency operation

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
25
Q

What two valves make up the Combined Intermediate Valves? Purpose of the two valves?

A

Intercept valve and intermediate stop valve

To protect the turbine against overspeed from stored steam in the cross around system

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
26
Q

Concerning the Combined Intermediate Valves, which valves are the ‘masters’ and which ones are the ‘slaves’?

A

CIV-4, 5, and 6 are the “slave” valves

CIV-1,2, and 3 are the “master” valves

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
27
Q

How do the Combined Intermediate Valves respond to a rapid load rejection?

A

Master valves will close to control the overspeed condition

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
28
Q

What happens when the Combined Intermediate Valve Master valves close 50%?

A

A slave closing limit switch is activated, which will trip closed the slave valves

29
Q

When would the Combined Intermediate Valve slave valves fully reopen?

A

When the master valves reopen to 90%

30
Q

Where is the Main Turbine Supervisory System located? What is its purpose?

A

Main Control Room

monitor main turbine shaft eccentricity, vibration, expansion, speed and valve position

31
Q

What is the Eccentricity Unit used for in the MT system?

A

To indicate and record shaft straightness while the turbine is on the turning gear, using an air-gap-type pickup detector

32
Q

How many speed sensors are on the Main Turbine?

A

Six magnet speed sensors – five are dedicated to the EHC speed control system and one to the Turbine Supervisory System

33
Q

Where is shell warming performed from in the MT system?

A

EHC control panel

34
Q

Warming starts prior to starting the turbine. When is Chest warming complete on the Main turbine stop valves?

A

At 515F

35
Q

When is the main turbine synchronized to the grid?

A

reactor power at 11.5-12.5% power

36
Q

What is the flowpath from the steam generators, through the main turbine, to the condenser?

A

four steam lines from the steam generators lead to the main turbine stop valves, then to the main turbine control valves, high pressure turbine, 4 moisture separator re-heaters, 6 combined intercept valves, 3 low pressure turbines, condenser

37
Q

What does the main steam system do for MT?

A

provides motive force for operation of the main turbine

provides 2nd stage reheating steam for Moisture separator reheaters

38
Q

How does the LO (lube oil) system support MT?

A

supplies and receives lubricating oil to the main turbine and generator bearings

39
Q

How does the GS (gland steam) system support MT?

A

Supplies sealing steam to main turbine shaft packing glands and receives shaft packing gland and turbine valve steam seal leak off.

40
Q

What is the main purpose of the Moisture Separator Reheaters?

A

improve the quality of the high pressure turbine exhaust steam before it enters the low pressure turbine

mechanically removes moisture and then reheats the dried steam

41
Q

Where are the MSRs in the MT system located? Which two MSRs are on the north wall?

A

176’ turbine building

A and C

42
Q

Regarding the MT MSRs, what is cold reheat?

A

the exhaust of the High Pressure Turbine going to the inlet of the MSRs

43
Q

What does Auxiliary steam do for the MT system?

A

supplies steam to the GS system to allow for main turbine startup.

sends steam to the reheater tube bundles during steam blanketing operation

44
Q

What does NN do for the MT MSRs?

A

instrumentation

45
Q

There is a line that branches off the C LP turbine supply from the MT MSR. Where does that send steam to?

A

Main Feed Water Pump turbines

46
Q

From the main turbine, where do the extraction points go?

A

3rd stage extraction goes to the 1st stage reheaters in the MSR and 7th feedwater heater

5th stage goes to the 6th feedwater heater

47
Q

How does IA interface with the MT MSRs?

A

operates low load valves and drain tank level control valves

48
Q

What are the two sections inside the MT MSRs?

A

reheater section and moisture separator section

49
Q

Where does the cold reheat steam enter the MSRs after leaving the high pressure turbine?

A

two inlet nozzles on the bottom of the MSR

50
Q

Which MSR tube bundle is supplied by HP turbine 3rd stage extraction? Which stage is supplied by main steam?

A

1st stage

2nd stage

51
Q

Where does the condensate from the 1st and 2nd stages of the MSRs drain to? Where do the high level dump valves route the condensate to?

A

1st stage heater drains to 1st stage drain tank, then to 6th feedwater heater

2nd stage heater drains to 2nd stage drain tank, then to the 7th feedwater heater

main condenser

52
Q

What is the purpose of the MT MSR drain tanks? Where are they located?

A

where the moisture that’s removed from the cold reheat steam goes

under each MSR, overhead of the 140’ turbine building

53
Q

What is the purpose of the two air operated level controllers associated with the MT MSR drain tanks? When will the high level dump valve fail open?

A

normal level control valve directs effluents to the heater drain tank

high level control valve directs effluents, when level gets too high, to the main condenser

when the turbine power is less than 10% and turbine shell warming is not in progress

54
Q

Say the MSR drain tanks are filling faster than the high level dump valve will drain to the condenser. At what level in the MSR will the main turbine trip?

A

3 inches

55
Q

How is the 2nd stage of the MT MSR steam supply controlled?

A

reheat steam high load valve and low load valve

56
Q

What is the purpose of the MSR 1st and 2nd stage reheater drain tanks? Where do the contents go after these tanks when flow is through the normal level control valve? High level control valve?

A

receives the condensate of their respective tube bundles in the MSR

1st stage goes to the 6th stage feedwater heaters

2nd stage goes to the 7th stage feedwater heaters

both go to the main condenser on high level

57
Q

What type of logic is used for the Main Turbine load pressure switch to prevent single point failures? Where is load sensed?

A

2 of 3 logic

inlet of LP turbine A

58
Q

What is the sequence for putting the 1st and 2nd stages in the MSRs in service as turbine load increases?

A

turbine at rated speed, minimum load, 1st in service with high level control valves open below 10% turbine load. Above 10% turbine load, normal level control valve in service

2nd stage in service after 1st stage with high level control valve open below 20%. Above 20% normal level control valve in service

59
Q

Concerning the MSRs, what is steam scavenging?

A

To prevent condensate collection in the tubes, an orificed line is connected from the top of the 1st and 2nd stage reheater drain tanks to the respective feedwater heater that the drain tank discharges to.

With the feedwater heater at lower pressure than the reheater stage, an excess of steam flow will now occur and sweep all condensate from the MSR reheater section tubes to drain to the drain tank.

60
Q

Concerning the MSRs, what is Air purging? What is done as an additional means of assisting this process?

A

to evacuate air from reheater tube bundles, prior to the admission of any steam to a bundle to ensure uniform heating as the bundles pressurize.

If steam were to be admitted to an unpurged bundle, the top half of bundle would heat first until steam reached bundle bottom half, causing severe differential expansion and possible resultant tube failure. Air purging is performed prior to admitting reheat steam or steam blanketing steam

reheater stage drain tank drain valve is opened to the condenser to empty the tank and expose it to condenser pressure

61
Q

Concerning the MSRs, what is steam blanketing? What type of valves are used to supply AS steam? What temperature is blanket steam?

A

pressurizing the reheater tube bundles to prevent condensation on the tubes, causing corrosion.

motor-operated stop check valves

300*F

62
Q

Concerning the MSRs, what is leak detection?

A

leaks in the 1st and 2nd stage tube bundles are found while online by measuring flow rate through orifice flow meters. deviations of more than 10% indicate a leak

while securing the steam blanket, the steam pressure decay rate is monitored

50% over one hour is normal

50% drop in a minute is a potential tube leak

63
Q

What are the effects of losing a MSR? Can the 2nd stage tube bundles be in service when 1st stage is not?

A

pressure boundary failure would shut the plant down

tube leaks or reheating steam issues would call for taking the 2nd stage tube bundles out of service or both stages out of service

no. 1st stage can operate without 2nd stage, but not vice versa

64
Q

What is the purpose of the MSR relief valves? Where are they located?

A

In the case that a Combine Intermediate Valve closes, the relief valve will pop open and relive full steam flow to the exterior of the turbine building

(MSR relief valve relieving pressures are staggered between the MSRs)

on the top of each MSR

65
Q

How does the main turbine system interface with the ED (extraction steam and drain) system?

A

Receives extraction steam and MSR reheating steam to preheat the condensate and feedwater before it enters the steam generators.

66
Q

What is the purpose of the inter-stage diaphragms and shafting packing in the main turbine?

A

diaphragms help direct steam at the turbine blades

shaft packing helps prevent leakage along the shaft, directs steam to the turbine blades and prevents steam from leaking out/air leaking in to the turbine

67
Q

Concerning the LP turbine rupture disks, they are normally dished inward. What happens when 5 psig is reached in the turbine exhaust hood?

A

rupture disk dishes outward against a cutting knife and relieve exhaust pressure to the atmosphere

68
Q

When does the overspeed trip device trip the main turbine?

A

110% or 1980 rpm

69
Q

What is the purpose of the main turbine drain valves?

A

depressurize the steam piping upstream and down stream of the HP and LP turbine, hot and cold reheat lines, MSR shell and ED steam lines and directs the steam to the main condenser