What areas are provided with recirculation air handling units the Aux Building?
CEDM cabinet room/MG set room
Charging Pump rooms
Areas below what level in the Aux Building are isolated from the normal HVAC system on a receipt of a SIAS?
100’
What system provides cooling to the HA Essential System ACUs?
Essential Chilled Water
How does HA and EW interact?
EW provides start/stop signals to HA ACUs when the EW pump is started/stopped
HA ACUs provide cooling and ventilation in the rooms in which EW system pumps are located
What system provides the motive force for various HA dampers?
Instrument Air
What components of the HA system are powered by NG?
Aux Building AHU Outside Air Heater, Access Control Area Normal AHU heating coil
During normal operations, what is the status of the HA Essential HVAC room coolers?
Standby
What maintains the lower levels of the Aux Building under a slight negative pressure after a SIAS?
Fuel Building/Aux Building Exhaust Essential AFUs
What is the capacity of the HA Outside Air Normal Supply AHUs?
50% each
Which Units have had its ‘A’ HA Outside Air Normal Supply AHU OIC replaced with filter media? Which AHUs still have the oil impingement cleaners?
Unit 1 and 2 ‘A’ units have filter media
all others have OIC
What is the purpose of the electric timer utilized in the OIC on the OSA Normal AHUs in the aux. building?
Controls a motor which intermittently rotates the filtering curtain through an oil bath
What situation would have us bypass the HA OSA normal AHU OIC timer and where can this switch be operated?
High dust loading conditions
operated from the control room
What provides cooling to the HA Outside Air Normal Supply AHUs?
Normal Chilled Water
What is the purpose of the HA Outside Air Normal Supply AHU interlock?
To ensure that the number of running AHUs are equal to or less than the number of running exhaust normal AFUs, which will maintain the Aux Building at a slightly negative pressure
What could be an adverse effect of air flow imbalances?
Fire dampers not being able to close in response to an actuation
Concerning the Access Control Area Ventilation system, what is meant by a dual duct AHU?
It takes suction from a single supply duct and distributes air to two distribution ducts
What provides the necessary heating for the hot duct in the Access Control Area Ventilation system?
Electric heating coil located in parallel with the cooling coil within the AHU
In regards to the Access Control Area Ventilation system, what provides the cooling water through the coil? What does the system provide conditioned air for?
Normal Chilled Water
RP island, labs, and RP locker rooms
What prevents Access Control Area Ventilation system normal heater operation when the AHU fan is not in operation?
A flow switch
What is the purpose of the mixing boxes in the Access Control Area Ventilation system? How many zones are associated with the system?
Controls air temperature by using pneumatic dampers to control air volume from the hot duct, cold duct air flow is not modulated and is full open
7 zones
How many Charging Pump Room Normal ACUs are there? What controls cooling flow through the unit?
Three ACUs (one per room)
auto flow regulating valve
When do the Charging Pump Room Normal ACUs start and stop?
On a receipt of a pump running signal
When the signal clears, a time delay actuates and maintains the ACU running for 5 minutes
What is the capacity of the CEDMCS Room Normal ACUs and what do they cool?
Two 100% capacity redundant ACUs
circulate air in the CEDM cabinet and MG Set rooms