HJ-Control building HVAC Flashcards
[HJ]
[HJ] purpose?
Provides the required environment for personnel occupancy and equipment operation in the Control Building, including the Control and Computer Rooms during normal and emergency plant operation
Also responsible for isolating the Control Room against intrusion of poisonous gases, smoke or airborne radioactivity from the outside
[HJ]
To what level of radiation exposure does the HJ system limit personnel to during an event?
5 Rem
How does HJ supports operations during a Station Blackout?
Provides environment to support equipment operation during the 16 hour coping period following a Station Blackout
What rooms does the HJ AHU supply on the 74’ level?
Air Handling Equipment Rooms A and B
What rooms does the HJ AHU supply on the 100’ level?
Train A and B Switchgear Rooms
Class A, B, C, D battery rooms
Remote Shutdown Rooms
DC Equipment Rooms
What rooms does the HJ AHU supply on the 120’ level?
Lower Cable Spreading Room
Inverter Room and Communication Equipment room
Corridor
What rooms does the HJ AHU supply on the 160’ level?
Upper Cable Spreading Room
Microwave Room
Lobby
What system provides the makeup water for HJ Normal OSA AHU air washer? What provides the spray motive force?
Domestic Water
air washer pump
Where are the HJ Outside Air Normal AHU and Air washer pump located?
74’ level Control Building
Where does the Control Room Normal AHU take suction from and where does it discharge to?
From an intake plenum being fed from:
120’ Communications Room and Inverter Room
140’ level
Control building OSA Normal AHU
Discharges back to the Control Room Complex, Comms Room, and Inverter Room
Where does the Control Building AHU take suction from? Where is it located?
The Control Building normal return duct and the outlet of the Control Building OSA Normal AHU
74’ control building
What is the purpose of the ESF Switchgear Room Normal AHU?
Assists the Control Building Normal AHU in cooling the DC equipment and ESF Switchgear rooms
When would the Control Room Essential AHU be used? Where is it located?
Starts on a SIAS, CSAS, CRVIAS, CREFAS or LOP
74’ control building
When would the ESF Switchgear Room Essential AHUs be used and where do they send air to?
SIAS or LOP, will send conditioned air to the ESF switchgear rooms, battery rooms, and remote shutdown rooms
When would the ESF Equipment Room Essential AHU be used and where does it send air to?
SIAS or LOP, will send conditioned air to the DC equipment, ESF switchgear rooms