Residual Heat Removal System (RHR) Flashcards

1
Q

What causes a RHR pump to Auto Start

A

L1 17.8”
1.68#s in DW

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

P1 A/B RHR Pump Trips

A
  1. Loss of suction path
    - MOV1 (supp pool suction) closed
    OR
    - MOV2, 112, 113 closed
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

When does RHR pumps realign to inject?

A

Always re-aligns to inject except SDC. The pump will trip if in SDC.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Is LPCI mode OPERABLE during Supp Pool Cooling?

A

LPCI Mode is INOP during Supp Pool Cooling due to the time required to align to LPCI Mode.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

How many starts in succession are allowed from ambient temp?

A

2 starts
After the 2 starts a 60 min wait is required.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

How many starts in succession are allowed from rated temp?

A

1 start
After the attempted start a 60 min wait is required prior to subsequent starts.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What must be done when aligning B RHR return to supp pool and why?

A

2RHS*MOV4C must be closed due to the potential for air getting into P1C in the event of a LOOP/LOCA.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What is the desired Supp Pool level when preparing to drain the Rx Cavity?

A

196.5’

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What is MAX total Drive Flow during an outage?

A

5,700gpm
- protect incore instrumentation.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What are the Interlocks for MOV1 Supp Pool Suction valve

A
  1. MOV2 A/B must be shut (prevent draindown)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What are the Interlocks for MOV2 SDC Suction valve

A

MOV1, 33, 38 A/B must be shut. (prevent draindown)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What are the Interlocks for MOV8 A/B HX bypass valves

A

Opens on a LOCA with a 10 min seal-in. If manually closed it will re-open. This is to maximize LPCI flow.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What are the Interlocks for MOV33 A/B Supp Chamber Spray valves

A
  1. Closes on LOCA (maximize LPCI)
  2. Manual Open during LOCA. (amber light)
    - LOCA signal in
    - MOV24 shut
    - DW >1.68#s
    - auto closes when DW <1.68
  3. Normal Ops - can only open if MOV2 A/B shut
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What are the Interlocks for MOV15/25 A/B DW Spray valves

A
  1. Both can open if:
    - LOCA signal
    - DW>1.68
    - MOV24 shut
  2. Does NOT auto close.
    - DW pressure <1.68 valve will stop where it is and must be manually closed.
  3. Normal Ops - can only open 1 at a time.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What are the Interlocks for MOV38 A/B/C Supp Pool Cooling valves

A
  1. Closes on LOCA
  2. Can override Open during LOCA with MOV24 shut. Amber light wil clear when LOCA signal is reset.
  3. Normal Ops - Can open if MOV2s are shut.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What are the Interlocks for MOV24 A/B/C LPCI injection valves

A
  1. Opens with LOCA signal
    AND
    - <130psid discharge to RPV (~480#s RPV)
    - Can be manually closed (amber light)
    - Will stay overridden until the LOCA signal has been manually reset on PNL 601.
    - Will NOT auto open if overridden
    - Will continue to stroke open with motor overload with LOCA signal. (Throttleable if no LOCA)