Condensate Iron Prefilter Sys (CFS) Flashcards

1
Q

What is the power supply to the Air Compressor

A

US-8

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

How do the condensate Iron Prefilters valves fail?

A

Fail, AS IS.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What does the Backwash Reveiver Tank Pump trip on?

A

Low discharge flow
(60 gpm w/ 10 sec TD)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is the purpose of the Condensate Iron Prefilter System?

A

Provides removal of suspended solids, particularly iron, so as to effectively eliminate the solids loading on the downstream Cond Demins

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What is the function of the CFS Air Compressor?

A

Supplies air to receiver, supports backwash (175 psig)
(cooled by CCS)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What is the backup air supply for the iron prefilter system?

A

Service Air

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What happens to prefilter inlet/outlet and backwash header valves on a loss of air, general power, or PLC?

A

All prefilter system inlet and outlet valves along with the backwash header isolation valve fail as-is

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What happens to Prefilter Backwash Valves, Backwash Header Vent Valve and BWRT discharge valve on a loss of air, general power, or PLC?

A

Fail Closed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What happens when an “INCOMPLETE BACKWASH” alarm is generated?

A

The entire backwash sequence must be re-initiated

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What does the phase separator transfer pump trip on?

A

9%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What kind of water is used for a backwash?

A

High Velocity Water

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What BWRT level is the Backwash sequence aborted?

A

High-High level alarm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What must be done if the prefilter d/p goes above 10 psid?

A

The Backwash Air Permissive Setpoint must be reset to 140 psig to prevent possible damage to the filter septa.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

How long is the phase separator tank recirced?

A

30-55min

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What is MAX d/p across a prefilter?

A

10 psid

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What step can the backwash cycle NOT proceed beyond with a HIGH BWRT level indication in?

A

PRESSURIZE step