Digital Electro-Hydraulic Control System (DEHC) Flashcards
What is the Purpose of DEHC?
Maintain Reactor pressure set point by positioning Main turbine steam supply and bypass valves
When does the STBY pump start.
System pressure <1300#
What is Drop2/52?
Redundant pair of controllers used for turbine protection functions
What is Power Load Unbalance?
- Compares Generator Current (amps) and Cross around piping pressure (43% mismatch)
- Active when Generator loaded to greater than 42.8%.
- =load reject
What happens on a loss of air to the EHC HPU drain cooler temp control valve?
Fails Open
What happens on a loss of CCS?
EHC reservoir temperature will go up and ultimately affect EHC pump NPSH
How long will BPV accumulators hold BPVs open?
1 min after Turbine trip
Purpose of Fullers Earth
Maintains the fluid at a low neutralization number by absorbing acids and water and maintains the chlorine content of the fluid within the recommended limits.
What actions need to be taken when resetting the Turbine and DEHC Speed automatically selects 1800 RPM?
Operator has approximately 10 seconds to select ALL VALVES CLOSED to prevent NSSS MSIV isolation on low vacuum trip due to Turbine Stop Valves opening. (N2-OP-21_D.10)
What does 20% Bypass Valve Jack Target equal in regard to Bypass valves?
1 BPV full open
When do BPV go closed in regard to Condenser vacuum?
7” Hg
What doe the colors Gray or Orange mean on the Drops?
INOP
What does a loss of IAS do to the EHC HPU drain cooler temp control valves?
Fail Open
MAX Cooling
What does Main Generator 86 mean?
armature fault