HVH/HVG Flashcards
What Rx Pwr are the Aux HXs used for HVH?
0-5% pwr
What Rx Pwr are the Intermediate HXs supplied from Aux Steam?
5-70% pwr
What Rx Pwr are the Intermediate HXs supplied from Extraction Steam?
70-100% pwr
What trips the HVH pumps P1 A/B?
Low discharge pressure (<=220psig, 10sec TD)
What are the auto starts for the HVH pumps P1 A/B?
NONE!
What must be done to the HVH make up water pumps if MWS is lost?
PTL
What is the power supply for HVH P1 A/B?
US10
Why must HVH be kept pressurized?
Keeps ASS out of HVH and prevents boiling.
What happens in winter to HVH on a loss of RB glycol?
- HVH Demand goes up
- RB Temp goes down
- Delta P goes down
- HVH Temp goes up
What does glycol prevent?
prevents coils from freezing
Where is HVH extraction steam supplied from?
8th Stage
How many HVH HXs are needed to be in service?
2
What must HVH HXs have before admitting Steam?
Must have flow before admitting steam. Steam supplied will shut w/out flow.
When will the HVH P2s not start?
<6”
What happens to steam supplied on a HVH pump trip?
They shut.