Misc Ventilation Flashcards
Where do the FN3s draw air from and send it?
They draw air from the common corridor, into CR, and into diesel room. (FN5 supplies corridor)
When do FN1s/2s start in Misc vent?
These fans are normally in STBY. They start when the diesel starts. They must be manually secured. 2 dampers modulate to maintain 80F in the room.
When do FN3s trip.
When FN1/2s start on a diesel start.
What outdoor temp declares DIV I&II INOP?
100F
What outdoor temp declares DIV III INOP?
103F
What must be done when it is 65F in the EDG rooms?
- Hourly Checks - Bases - the EDG could be reluctant to start at lower temps.
- Governor must be >70F. Start diesel before going below 70F on the governor.
When will a FN1/2 restart automatically?
Red flagged following a loss of power to the bus.
What do FN4 A/B provide ventilation for?
DIV I, II, & III battery rooms
When do FN4s autostart?
Trip of running pump
Are smoke fans manual or auto start?
Manually started
When do DIV I, II & III battery room exhaust fans trip?
CO2 discharge.
When are safety related Unit Coolers considered to be INOP?
When they do not have cooling water.