Fire Protection/Detection Flashcards
What is the power supply for the Electric Driven Fire Pump?
SWG012
When do fire protection maintenance pumps start?
Lead - 120 psig
Lag - 110 psig
When do fire protection maintenance pumps shut off?
135 psig
When does the electric motor driven fire pump (P2) start?
90 psig
When does the diesel driven fire pump (P1) start?
85 psig
What are the Fire Pump Auto Mode trips?
Overspeed @ 120%
What are the Fire Pump trips in Test Mode?
- Overspeed (>120%)
- Low oil (<8 psig)
- High Engine Cooling Water temp (>205F)
What are the Fire Pump Man ‘A’ or ‘B’ Mode trips?
NO TRIPS
What is the Power Supply for CO2 Storage Refrigeration Unit REF1?
US1C
What is the Power Supply for CO2 Storage Refrigeration Unit REF2?
US3C
When do CO2 tank generator purge valves AOV186/187 trip?
CO2 tank low level, 68%
What is the TD for Halon initiation?
30 sec
What is a secondary purpose of the Fire Protection CO2 tanks?
Purge the Main Generator
What are the Zone Abbreviations?
S - Single
X - Cross Zone
N - No Auto
G - Halon
F - Foam
L - Low Press CO2
W - Water
Z - no supp
What are FPF-P1A/B Trips?
- Out of position valves
- Motor Overload
- Low Tank Level (<5”)
What are the Hose Reel Pump trips?
- Out of position valves
- Motor Overload
- Low Tank Level (<5”)
- > 175# for 20sec and NO FLOW