Aux Steam System (ASS) Flashcards
What happens on a loss of HVH to the RB?
Goes positive.
What happens to MOV16 on a CSR Hi-Hi?
closes (mov3 opens)
What happens to MOV3 on a CSR low level
closes (mov16 opens)
What systems supply Aux Steam?
Main Steam, Extraction Steam, Aux Boiler.
What systems can Aux Steam supply?
SJAEs, Offgas Preheaters, CSRs, Building Heating Aux HX, Building Heating Intermediate HXs
What systems can Extraction Steam supply?
CSRs, Building Heating Intermediate HX.
What systems can the Aux Boilers supply?
SJAEs, Offgas Preheaters, Building Heating Aux HXs.
What are the Aux Steam reducer setpoints for its supply systems?
SJAE: 128#
HVH: 110#
Offgas Preheaters: 96#
CSRs: 95#
Steam Seals: 7#
What is the Conductivity Limit for the Aux Boilers?
2100 umhos/cm
What can trip the Aux Boiler Feed Pump?
- Deaerator Low Level
- Low pump discharge pressure (<125psig, 10sec)
- Motor Overload
Why are chemicals added to the Aux Boilers?
To raise pH