High Pressure Core Spray (CSH) Flashcards
What happens on an Initiation seal-in rest for Level and Hi DW?
L2 will override the reset. The Hi Dw will reset but the pump will stay running.
What does HPCS maintain in RPV on a 1” line break?
Maintain >L1
Prevent ADS
Cover TAF
When does min flow valve MOV105 open?
<634gpm and >240#
What is required for Hi DW pressure or Level detectors?
A or B
AND
C or D
What changes will occur on an inadvertent initiatoin of HPCS?
- NR lvl increase (stable at higher lvl)
- APRMs decrease (low pressure, more voids)
- Steam Flow decrease (more power spent heating water)
- Feed Flow decrease (compensates for water addition from HPCS)
- Pressure decrease (restored by EHC to new lower value)
- MWe decrease (subcooling increased, reduced efficiency)
What happens to CSH-MOV110, 112 (CST return line valves) on initiation?
Auto Close on system initiation
What does the L8 TEST keylock switch bypass?
L8
When does HPCS suction swap from CST to Supp Pool?
CST @ 97”
OR
Supp Pool @ 200.52’
(suctions do not realign on initiation)
What are MOV101 (CST Suction Valve) interlocks?
- Closes when MOV 118 (Supp Pool suction valve) is 95% Open
- MOV118 must be closed in order to Open
What are MOV118 (Supp Pool Suction Valve) interlocks?
- Will not open if MOV110, 112 (CST return valves) are open.
- Can Override closed.
- MUST Shutdown pump to realign to the CST.
- Auto open if, supp pool >200.52 or CST <97”
What are MOV111 (Supp Pool return Valve) interlocks?
- Auto closes on system initiation.
What are CSH-MOV107 (RPV Injection Valve) interlocks/features?
- Opens L2, 1.68#DW
- Closes L8
- Override = Amber light
- Still moves with overload. Throttleable if stroking manually.
- Will always auto open on L2, no matter what!
- Cannot be made throttleable below L2
- Only auto closure is L8.
what needs to be verified if depressing high water level reset?
Verify Open MOV107 if below L8.
What are HPCS OPERABILITY ties with P2 (Jockey Pump)
- 47ft required in CST if P2 is INOP.
- If <47ft and Hi Point Vent alarm is in, CSH is INOP and Unavailable.
What must be done in the CSH system in order to realign from supp pool to CSTs?
Shutdown the pump