Condenser Air Removal (ARC) Flashcards

1
Q

What cools the Seal water Cooler?

A

Service Water

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is the Air Ejector Precooler cooled by?

A

Service Water

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What cools the Intercondenser?

A

Condensate

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What are the pump trips for the 2ARC-P1A/B pumps?

A
  1. Pump running with respective seal water flow low (<10 GPM) for longer than 10 seconds
  2. Main steam line radiation level high-high (3XNFPB) or radiation monitor inoperative
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What is the mechanical vacuum pump precaution?

A

Do not operate the Mechanical Vacuum Pumps with Reactor Power greater than 5% as indicated on APRMs. The plant exhaust stack is not detonation proof.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What happens to AOV105 on a MSLHR alarm?

A

closes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What needs to be verified prior to placing the Hoggers in service?

A

Verify no fuel element failure.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What is the purpose of the silencers on the outlet of the hoggers?

A

Reduce vibrations.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What can the hoggers NOT be operated without?

A

Seal Water

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What happens on a  High-High rad (3 x NFPB) or Rad Mon INOP?

A

Trip vacuum pumps 2ARC-P1A/B and close 2ARC-AOV105. (Control Rod Drop is the bases)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What should be used when starting system immediately after a SCRAM?

A

USE CAUTION

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

When shall the Turbine be manually tripped?

A

<24.6”vac & <410 MWe (30%)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What shall be done if condenser vacuum is approaching 22.1”Hg?

A

Trip the Turbine.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What Condenssate level shall the hoggers not be operated?

A

> 264 ‘ elevation. Suction piping is at 266’.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What is the purpose of V47 in the ARC system?

A

maintains min flow & dilutes H2.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly