Condenser Air Removal (ARC) Flashcards
What cools the Seal water Cooler?
Service Water
What is the Air Ejector Precooler cooled by?
Service Water
What cools the Intercondenser?
Condensate
What are the pump trips for the 2ARC-P1A/B pumps?
- Pump running with respective seal water flow low (<10 GPM) for longer than 10 seconds
- Main steam line radiation level high-high (3XNFPB) or radiation monitor inoperative
What is the mechanical vacuum pump precaution?
Do not operate the Mechanical Vacuum Pumps with Reactor Power greater than 5% as indicated on APRMs. The plant exhaust stack is not detonation proof.
What happens to AOV105 on a MSLHR alarm?
closes
What needs to be verified prior to placing the Hoggers in service?
Verify no fuel element failure.
What is the purpose of the silencers on the outlet of the hoggers?
Reduce vibrations.
What can the hoggers NOT be operated without?
Seal Water
What happens on a High-High rad (3 x NFPB) or Rad Mon INOP?
Trip vacuum pumps 2ARC-P1A/B and close 2ARC-AOV105. (Control Rod Drop is the bases)
What should be used when starting system immediately after a SCRAM?
USE CAUTION
When shall the Turbine be manually tripped?
<24.6”vac & <410 MWe (30%)
What shall be done if condenser vacuum is approaching 22.1”Hg?
Trip the Turbine.
What Condenssate level shall the hoggers not be operated?
> 264 ‘ elevation. Suction piping is at 266’.
What is the purpose of V47 in the ARC system?
maintains min flow & dilutes H2.