Remote Management Capability Flashcards

TRA00377

1
Q

Where is the RMC located?

A

TRA 680 ECC.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What functions are provided in the RMC system?

A

Rx Scram
Rx Reverse
CDS Monitoring
DCS Control and Monitoring
IVPAMS
Manual Vessel Vent Operation
Manual EFIS Injection Valve Operation
EFIS Pressure Trip Bypass

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is the safety significance of being able to operate Vessel Vents?

A

Depressurize the primary and allow firewater to cool the core.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is the importance of EFIS pressure trip bypass?

A

Prevent unnecessary introduction of firewater into the vessel during depressurization of the primary.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What are the power components related to RMC?

A

680-E-59 UPS battery
680-E-58 RMC UPS
680-P-52 RMC Power Panel
680-E-56 RMC UPS Maint Bypass Switch
680-E-57 RMC Manual Transfer Switch.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Is the RMC a safety-related system?

A

No.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What are the power sources for RMC?

A

Comm Power
ECC Diesel
Portable Diesel
Battery-Backed UPS

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

How long can RMC UPS Battery Power to the RMC?

A

Minimum of 2 hours.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What supplies power to the RMC interface power supplies in the PPS rooms?

A

50 vdc from 680-E-50 to PPS power supply cabinets which is regulated to 24 vdc.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What voltages are used and supplied by RMC?

A

120 vac and 24 vdc to TRA-680 components
50 vdc reg to 24 vdc for PPS interface.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What ATR system actuations require BOTH RMC jumpers?

A

EFIS pressure trip bypass and Rx Scram.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What RMC status indication is available in the PPS room?

A

PPS interface power supply cabinet has a light that illuminates when RMC is energized with jumpers installed.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What does AOP-0.1 require operator to place one LOCA inlet pressure bypass switch to BYPASS?

A

On a CLOFA, operators will be able to restart a PCP from the RMC.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What cause the ECC Remote Capability Active annunciator to alarm in the RCR?

A

Power is supplied to the voltage regulator of any PPS interface power supply cabinet.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

How do you know if communication is established with PPS room from the RMC Panel?

A

Firewater injection level and pressure meters will show indication. There is also a comm link for PPS D light on 680-P-51.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

How can you diagnose an RMC Power Supply failure from the RMC Panel?

A

Results in dark indication. If power supply has failed to PPS interface, 680-P-51 indication will be lit but indicate low scale.