Console Display and Annunciator System Flashcards

TRA00065

1
Q

What is the purpose of the CDS?

A

Provide Real-Time plant status information during all operating conditions.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is the purpose of the annunciator system?

A

Provide audible and visual warnings of abnormal plant status during all operating conditions.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Draw a simplified one-line diagram of CDS

A
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Where do filed input signals go in CDS?

A

Supplied to both SER unit and to both RDAS computers (DAC/DAN)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What is the function of the SER units in CDS?

A

SER units determine if signal value exceeds setpoint values and will process an alarm to the annunciator monitors and horn.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What is the function of the RDAS computers in CDS?

A

RDAS computers provide signal data to the CDS displays which also indicate process values that are in alarm status.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Where are the 52-inch monitors for CDS located?

A

CDS monitors are located in the RCR

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What are the power supplies for the 52-inch annunciator monitors?

A

Powered from 670-IP-1 through 670-E-1384

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

How do you select between DCS and CDS inputs on the Spare #1 monitor?

A

Source select switch on front of Spare #1 monitor

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Give RCR CDS Workstation monitor power supplies.

A

Station 1 - Instr UPS E-106 from E-117
Station 2 - Instr UPS E-106 from E-117
Station 3 - Instr UPS E-106 from E-117
Station 4 - Utility UPS E-30 from E-115
Station 5 - Utility UPS E-30 from E-115
CRS Station 6 - Utility UPS E-30 from E-115
SRAO Station 7 - Instr UPS E-117

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Where are CDS Work Stations located?

A

5 on reactor control console
1 on CRS station
1 in the process control room

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What is the annunciator horn power supply?

A

Powered from E-1384 (fed from IP-1)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What functions do SER units fulfill?

A

Receive field inputs from plant equipment
Monitor inputs for a change in state
When parameters exceed alarm values processes alarm signal to the annunciator servers and to the CDS

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What does SER stand for?

A

Sequence of Events Recorders

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What are the power supplies for SER racks?

A

On the left side of each rack is a 15V power supply which is powered from one of two Pulizzi power controllers

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Which racks are powered by SER-1?

A

115V supply to 15V for Racks 00 and 02

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

What racks are powered by SER-2?

A

115V supply to 15V for Racks 01 and 03

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

What are the LED indications for SER output cards?

A

LED on - card is functioning normally
LED off - card has detected an error or is offline

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

Describe SER printers.

A

2 printers:
RCR off right side of upright
RDAS room on table on North wall

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

Where are Cable Concentrator System Cabinets located?

A

TRA 608 Demin Bldg and TRA 670 ATR RDAS Room

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

What are the power supplies to the CCS Equipment Units 1 and 2 in TRA 608?

A

Unit 1 - LP-A (Commercial)
Unit 2 - LP-E (Comm/Diesel)

22
Q

What are the power supplies to the CCS Equipment Units 1 and 2 in TRA 670?

A

Unit 1 - 670-LP-5 (Commercial)
Unit 2 - 670-LP-5 (Comm/Diesel)

23
Q

Where is the 608 CCS cabinet located?

A

Behind the upright annunciator panel next to MCC-1 and 2

24
Q

What 3 indications occur on an alarm received by the SER from the Utility Area via CCS?

A
  1. Audible alarm in RCR
  2. Overhead Annunciator Panel 4 window activates
  3. Alarm notification will be received on console CDS for Panel 4
25
Q

What occurs on a failure of one of the CCS pathways?

A

Half the alarm box supplied by that system will turn red and not function normally

26
Q

What is contained in CDS cabinet 1 for RDAS?

A

Pulizzi power controllers (3)
DAC and DAN Network Switches
Annunciator Servers 1-6

27
Q

What is contained in CDS cabinet 2 for RDAS?

A

Pulizzi power controllers (2)
Time SErver
Alarm/Displays Computers
Work Station Computers 1-7
HMI Network Switches
Work Station KVM module 1-7

28
Q

What are the power supplies for Pulizzi Power Controllers?

A

E-30 and E-106

29
Q

Where is the TYP/INL DAQ Network Switch located?

A

RCR SER Cabinet on top of Rack 00

30
Q

What is the function of the DAQ network switches?

A

Route data to different devices within the CDS and annunciator system.

31
Q

Where are the DAS and HMI Network switches located?

A

CDS Cabinet 1 and 2 in the ATR RDAS Room

32
Q

What is the power supply for DAC network switch 1?

33
Q

What is the power supply for DAN Network switch 2?

34
Q

Where are the Work Station computers located?

A

CDS Rack 2 in the ATR RDAS room

35
Q

What are the functions of the Alarm/Display computers?

A

Receives, processes and communicates SER alarm information to the rest of the console display system
Maintains system configuration

36
Q

What is the purpose of the I/O Configuration Work Station?

A

Used by RICTs to work on and troubleshoot any part of the CDS

37
Q

What is the power supply for the RDAS DAN?

A

Instrument UPS through E-106

38
Q

What is the power supply for the RDAS DAC?

A

Utility UPS through E-30

39
Q

What does CDS red flashing display mean?

A

SER Alarm or Window Message pending

40
Q

What does CDS red solid display mean?

A

Plant parameter in alarm state or incomplete procedure panel path

41
Q

What does CDS yellow display mean?

A

Plant parameter in caution state

42
Q

What does CdS green display mean?

A

Plant parameter normal state

43
Q

What does CDS cyan display mean?

A

Display title and division lines

44
Q

What does CDS dark blue display mean?

A

background color

45
Q

What does CDS brown display mean?

A

Inactive state or failed conditioned for indicated position

46
Q

What color are satisfied permissives in CDS?

A

Outlined green or solid green

47
Q

What is the color value equivalence for power split display?

A

Green - <101% abs, Yellow - 101-<103% abs, Red - >103% abs

48
Q

Describe how water power calculator is assigned.

A

Either WPC 1 or 2 can be assigned as main or alt.

49
Q

What does red indicate on Confinement Door position and seal status?

A

Red indicates a door is not shut

50
Q

What indicates an off-normal damper position on RMSS Damper Position Display?

A

Red indicates off-normal.

51
Q

What is the TSR consequence of a loss of both DAC and DAN?

A

Loss of LPCIS. Entry into TSR 186 3.6.1 condition c:
1. Position neck shim to nearest limit switch and cease further neck shim movement
2. OSCCs movement restricted to maintaining indication on the NL instruments consistent with the values at the time of RDAS failure
3. 48-hours to restore LPCIS or shutdown

52
Q

What is the TSR consequence of a loss of annunciator system?

A

Loss of canal level annunciator operability. 3.5.6 condition A:
1. Canal cask handling in progress - immediate and continuous local canal level monitoring if canal cask handling is in progress.
2. No canal cask handling in progress - canal level check within 15 minutes of the annunciator system loss and then continuing level verification checks every hour.