What is the purpose of CE?
Stator cooling provides cooling for: main generator stator windings generator bushings rectifier excitation system generator lower frame extension Isophase bus cooling: independent cooling for electrical buses from main generator terminals to the main power transformer and aux transformer
What is the pump and heat exchanger configuration in the stator cooling system?
2- 100% capacity pumps in parallel
2 - coolers in series
What cools the stator cooling heat exchangers?
TC
How is TC run through the heat exchangers?
it is run in parallel so that TC can be isolated to one HX and the other still be in service.
Describe the Isophase cooling system.
motor driven fan, air to water HX, and an air plenum to force air cool the isophase bus.
two units with a common air plenum, both operating at the same time.
What supplies makeup water to the stator cooling system?
DW
What cools the collector housing heat exchanger?
WC
What will cause the standby stator cooling pump to trip?
the in service pump’s discharge pressure falling below its low discharge setpoint. There is 2/3 logic for this.
What are the power supplies for the stator cooling water pumps?
NG
What is the capacity of the stator water coolers?
Each is 80% capacity, so if TC is removed from one of the coolers, generator load must be reduced to at least 80%
How does the stator cooling water temp control valve fail?
through the cooler
What is the purpose of the stator cooling storage tank?
NPSH for the pumps & to compensate for variations in water volume due to temperature and the presence of gases in the water.
What does the deionizer do?
maintain stator cooling water at a low conductivity by continuous removal of dissolved mineral salts in the mixed bed deionizer. It continuously deionizes 10% of the stator cooling flow stream.
Where can the automatic function of the standby stator cooling water pump be tested from?
control room or at the local control panel.
What happens to a pump that was auto started if the original pump returns to service?
it will continue to run until it is manually shutdown and returned to standby