What is the purpose of CE?

A
Stator cooling provides cooling for:
  main generator stator windings
  generator bushings
  rectifier excitation system
  generator lower frame extension
Isophase bus cooling:
  independent cooling for electrical buses from main generator terminals to the main power transformer and aux transformer
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is the pump and heat exchanger configuration in the stator cooling system?

A

2- 100% capacity pumps in parallel

2 - coolers in series

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What cools the stator cooling heat exchangers?

A

TC

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

How is TC run through the heat exchangers?

A

it is run in parallel so that TC can be isolated to one HX and the other still be in service.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Describe the Isophase cooling system.

A

motor driven fan, air to water HX, and an air plenum to force air cool the isophase bus.
two units with a common air plenum, both operating at the same time.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What supplies makeup water to the stator cooling system?

A

DW

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What cools the collector housing heat exchanger?

A

WC

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What will cause the standby stator cooling pump to trip?

A

the in service pump’s discharge pressure falling below its low discharge setpoint. There is 2/3 logic for this.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What are the power supplies for the stator cooling water pumps?

A

NG

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What is the capacity of the stator water coolers?

A

Each is 80% capacity, so if TC is removed from one of the coolers, generator load must be reduced to at least 80%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

How does the stator cooling water temp control valve fail?

A

through the cooler

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What is the purpose of the stator cooling storage tank?

A

NPSH for the pumps & to compensate for variations in water volume due to temperature and the presence of gases in the water.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What does the deionizer do?

A

maintain stator cooling water at a low conductivity by continuous removal of dissolved mineral salts in the mixed bed deionizer. It continuously deionizes 10% of the stator cooling flow stream.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Where can the automatic function of the standby stator cooling water pump be tested from?

A

control room or at the local control panel.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What happens to a pump that was auto started if the original pump returns to service?

A

it will continue to run until it is manually shutdown and returned to standby

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What pressure is stator cooling water supplied to the generator at and how is it controlled?

A

60 psig and it is controlled by using the pressure control valve PV-34 (normally locked throttled)

17
Q

How is flow controlled to the generator bushings and rectifier excitation system?

A

manually using FCV-12 & FCv-13

18
Q

What stator cooling water temperature does TV-33 maintain at the generator inlet?

A

42C

19
Q

How is cooling flow to the isophase bus controlled?

A

manually by throttling the cooler outlet valve

20
Q

Where are the isophase bus fans controlled from?

A

locally at the load center supply breakers (NG)

21
Q

How is the main generator collector housing cooled?

A

by a fan attached to the main shaft of the generator that circulates are over a heat exchanger that has WC flowing through it and then through the exciter unit.

22
Q

How does the stator leak monitoring system work?

A

it monitors the head tank vent for the presence of hydrogen.

23
Q

What else does the SLMS system do?

A

it provides a method of increasing stator cooling water O2 level by allowing for air injection into the system head tank.

24
Q

How long after a stator cooling water trouble alarm do you have to reset it or fix the problem before the turbine trips?

A

70 seconds.

25
Q

What must be done if isophase bus cooling is lost?

A

normal 34,000 amps may be maintained for up to 30 minutes, but after that, you must reduce to 23,000 amps for the unit to be as self sustaining cooling.