How much flow can one heater train bypass line pass?
25%. You can still get 75% flow through one train of HPFHs.
What is the purpose of feedwater system (FW)?
Provide feed water to the steam generators at the required pressure, temp, and flow rate
Provide the final 3 stages of feed heating in two parallel heater trains
What are the steam supplies to the FWPT and when are they supplying?
Aux steam - for uncoupled overspeed testing only
Main steam- when MT is insufficient (low powers)
MT - normal source from D MSR
What are the pressures of the condensate coming into the feed pump and feed leaving the feed pump?
350 psig going in and 1200 psig leaving the feed pump
How much feed flow can one feed pump handle?
65%, but we are limited to 62% on a down power
What pressure is seal water supplied to the MFP casing at?
150 psig
What differential pressure is maintained across the MFP seals?
15 psid
What has to be true in order for the HP stop valve on the FWPT to be opened?
The control valve must be closed.
How can you tell if the HP control valve is closed prior to stop valve testing?
A local green indicating light will tell you that the control valve is closed.
Which two FWPT steam valves are controlled by the same hydraulic operating cylinder?
The high pressure control valve and the low pressure control valve.
The LP opens first and if it isn’t supplying enough steam to get the turbine to the desired speed, the HP control valve will open.
Why does the LP stop valve only close half way when testing it?
Because the LP control valve is always open, so if it went full closed, you could not get it back open without shutting down the pump.
Why does the LP control valve on the FWPT close when the turbine is tripped?
Because when the turbine trip is reset, the stop valves go full open. This could be an uncontrolled start if the control valve wasn’t closed.
It also acts as a second line of defense to shut off all steam flow and prevent turbine damage.
How many stages are in a FWPT?
6 stages
Where are the FWPT drain valves controlled from?
The control room.
Lead drain lines drain upstream of the stop valve to prevent slugs of water to the turbine.
Normally closed, but bypasses with orifice plates to remove water are placed in service.
What interlocks must be met to start the FWP turning gear?
Oil pressure must be sufficient on the feed pump and the feed pump turbine.