Circ Water Flashcards
What is the purpose of the CW system?
Receive heat rejected by the turbine thermal cycle
Receive heat from the PW system
Use the cooling towers to dissipate the heat.
How does the CD system interact with the CW system?
The CW system provides a place to discharge condensate during overboarding.
It also removes heat from the condensate in the main condenser.
How many supply lines are there on the CW pump discharges?
two. A & B supply one and C&D pumps supply the second.
What is the normal position of CWN-V11?
The supply line cross connect is usually open when operating 3 or 4 pumps. It can be open if using 1 or two pumps if supplying through both loops is desired.
How do we fill the CW system after draining?
using the PW pumps discharging into the supply lines.
How are the “C” shell outlet water box vent lines different from the others?
There are relief valves on the vent lines, so installation of isolation valves was not permitted. The lines are stainless steel to reduce the likelihood of an unisolable leak.
Which cooling tower has both a PW return and a CW return in one header?
2 cooling tower
Describe the flow through the cooling towers.
CW lines deliver the water to the top of the cooling tower. => dispersed around the top via a distribution flume => flows into the distribution basin => flows through holes in the distribution ring over the tower fill media => into the collection basin => back to CW pump suctions
How many cooling tower fans are there and where do they take a suction from and discharge to?
16 fans that take a suction on the lower portions of the cooling tower across the tower fill media and discharge out the top of the cooling tower.
Why is there a constant feed and bleed on the CW system?
to minimize the build up of chemicals and impurities to keep them within the allowable limits. The major concern is silica that can plate out on the Ti tubes in the condensers.
Where does makeup water for the CW system come from?
it is provided by the storage reservoir via the TB system.
What supplies cooling water to the CW pump motor lube oil cooler?
TC
What chemicals are added to the CW system?
hypo
foam control agent
sulfuric acid
scale dispersant
What other items discharge to the CW intake canal?
low TDS sump pumps from the polishing demins
OW yard area sumps
Turbine building roof runoff
Spray pond backwash sump pump
How many trains of TB are there?
two, “A” (original old system blowdown currently unused, but makeup is used) and “B” (newer section that is used)