Freeze Protection & Heat Trace Flashcards
Which systems have freeze protection?
Systems with outdoor interfaces.
CH, NC, WC, CM, CW, PW, SC, CT, TB, DS, and DW
What supplies power to the freeze protection (QJ) system?
NH and QA (lighting) for only the water rec panel
What is heat trace power stepped down to from NH?
120VAC by a transformer located next to the control panel.
What does the white indicating light on the freeze protection panel indicate?
It indicates that the circuit is energized.
Which panel is the safety related panel for freeze protection?
QJN-C05 is in the CST pump room. It has a push button that clears the main control room alarm.
Where are the freeze protection heaters located on the equipment?
On instrument lines and pipes under the insulation.
What does it mean that the freeze protection lines are self regulating?
They respond to temperature variations anywhere along the heater length to protect against overheating even when the heater is overlapped.
What is the neutral wire for on freeze protection?
Provides electrical path for monitoring the continuity of the heater along its length.
What is the ambient fixed set point for the freeze protection panel thermostats?
40F (below energizes the heater and above deenergizes the heaters)
What freeze protection indications will cause an alarm in the control room?
Line thermostats will send an alarm if the temperature drops to 35F.
If CST piping heaters are energized there will be an alarm in the control room.
What is the normal condition of the freeze protection system?
Automatic standby mode.
What is the purpose of the heat trace (QM) system?
Maintain given temperatures associated with special processes. Heat control is maintained to prevent precipitation of concentrated material in the fluids.
What systems/components have heat trace?
Boric acid batching tank RMWT piping HUT piping RWT piping RU- 141/143 piping Hydrogen analyzers and PASS piping Solid Radwaste system LRS evaporator BAC
What can be found on the modular solid state controllers mounted on the heat trace control panel?
Controller set point indication on a calibrated dial Deviation meter High alarm light Low alarm light Heater on light
What heat tracing alarms are in the control room?
A trouble alarm is registered in the control room for any alarm signal in a local panel including panel power failure.