BISP CH 5 REF 1.7 Flashcards
It shall be unlawful to transmit____or more unnecessary alarms in any_____month period
2 or more alarms in any 3 month period
Is the malicious transmission of a false alarm by activation of a manual fire alarm box be construed as an unnecessary alarm
NO
What is a defined fire alarm system
Any system that automatically transmits signals to the fire department or a central station and that is installed in premises which are required to have a fire alarm system
The requirement to maintain an alarm log book applies to
any premises having a defined fire alarm system
Who is responsible to make all alarm log book entries
Fire safety director or a person designated by the owner if no fire safety director is required
Where is the alarm log book maintained
At the buildings main fire alarm control panel and made available for inspection by any Dept representative
In the absense of a secure location for the alarm log book at the main fire alarm control panel the alarm log book may be secured during non business hours in another area
provided it is made available for inspection by any dept rep responding to an alarm on the premises
How are alarm log book entries made
Chronological order recording the location and causes of all alarm signals transmitted by such fire alarm system
Failure to provide an alarm log book or providing such book without the required entires would require issuance of a
NOV
Requirements of alarm log book
Bound book other than spiral Consecutively numbered pages and lined Cover shall say "alarm log book" Name & address of building on cover All entries in ink and dated Separate log book for each year Maintained on premises for 3 years from date of last entry Log book divided into 4 sections
Daily alarm log book entries
Name
C of F #
Time started
Time relived
Activated alarm entries
Date and time activated
Location and detector type
Probable cause
Department unit and officer
System off line entries
Time off line
Reason off line
Central station name and phone number
Time restored
Notification entries
The date and time of any notification to occupants of the premises regarding a non functional or improperly functioning alarm system
Smoke detectors connected to a defined fire alarm system shall be cleaned not less than
Once every 6 months