Wet standpipes needed in buildings that are
3 or more stories in height with a floor area 7500 SQ FT or greater on any floor
Standpipes are not required in buildings occupied
Entirely by Group R-3
No more than 2 dwelling units (one and two family homes)
Long term basis
Group homes
Convents and monasteries fewer than 20 occupants
Explanation of lowest level of Fire Dept vehicle access
This should be taken to mean the lowest point a fire apparatus ,ay be driven in order to gain access to any portion of the building
Standpipe systems can have an
Outside contractor with a certificate of fitness
The maintenance and record keeping for standpipe systems requires
A person holding a C of F for standpipe systems (VO)
Standpipe systems must be inspected monthly (VO)
Five year hydrostatic test must be performed & records kept (A-8)
When pressure reducing valves are installed on a standpipe system a
Flow test must be conducted at least once every 3 years to demonstrate proper adjustment of the valves
VO or NOV for non compliance
If a standpipe system is not found but is deemed needed
Possible vacate
BC must respond
High Priority Referral Report