BISP ASSEMBLY PRE 2008 Flashcards
Under the 1968 building code, a minimum of 3 exits is required in Assembly spaces for _______ or more occupant loads
501
Under the 1968 building code a minimum of 4 exits is required in Assembly spaces for ______ or more occupant loads
1000
Under the 1968 building code, a minimum of 2 exits is required in Assembly spaces for _______ or more occupant loads
76
Exits signs are required in all Assembly spaces to indicate exits AND direction to exits and must be clearly visible from all parts of the Assembly space. The bottom of such signs shall be at least _____ feet above floor level
7
Exit signs shall be internally lighted where the general illumination in an Assembly space is reduced to less than _____ foot candles during a performance or during occupancy
5
All assembly spaces shall be provided with emergency lighting sufficient to provide at least ______ foot candles of illumination at the floor level
5
Regarding exit and corridor openings in assembly spaces, or would be correct to state
- The minimum corridor width is 44 inches
- Exit openings must be at least 36 inches wide for single doors for spaces up to 300 persons
- Exit openings must be at least 44 inches wide for single doors for spaces over 300 persons
- Exit openings must be at least 66 inches to 88 inches wide for doors swinging in pairs
Places of Assembly used as cabarets and all stages, dressing rooms and property rooms used in conjunction with places of assembly used as cabarets require
- A Supervised Fire Alarm Signal System
* A Sprinkler System throughout
Catering establishments and banquet halls with occupant loads over ______ persons require sprinkler systems
300
The following may be permitted in cellars, basements and other below grade areas if there is a sprinkler system in place throughout in places of Assembly
Class 2 Combustible liquids
Class 3 Combustible liquids
NOT permitted is Flammable liquids
Can LPG equipment and containers be used indoors for the purpose of performing emergency indoor repairs including such emergency use in an OCCUPIED place of public assembly
NOT allowed in an OCCUPIED place of public assembly
Cut natural tress may be displayed in what type of place of public Assembly?
Only Houses of Worship
Regarding spaces for standing audience members, it would be correct to state that rope, tape or other thin material must separate the space to be left clear at a height of ________ feet
3-4 feet
True or False
It shall be unlawful to stand, or allow any person to stand, in or at the head of an isle
True
How many row of persons are allowed to stand in balconies
1 Row