AOP-37 "Loss of Instrument Air" Flashcards
1
Q
AOP-37 entry conditions
A
- EK-1101 “Containment Instrument Air LO Press” (85 psig)
- EK-1102 “Instrument Air LO Press” (85 psig)
- EK-1103 “Service Air LO Press” (80 psig)
2
Q
AOP-37 automatic actions
A
- Standby Instrument Air Compressor(s) starts at 92 psig
- CV-1212, Service Air Header Isol, closes at 85 psig in the Instrument Air Header
3
Q
AOP-37 reactor trip criteria
A
Erratic equipment operation observed on equipment required for safe plant operation (may occur when Instrument Air pressure approximately 50 psig)
4
Q
AOP-37 immediate actions
A
NONE