AOP-10 "Loss of Bus 1E" Flashcards
1
Q
AOP-10 entry conditions
A
Symptoms of loss of Bus 1E (loss of power to all Bus 1E powered components) in conjunction with 1 or more of the following:
- EK-0517 “2400V Bus 1E Undervoltage” (90V secondary or 1860V primary)
- EK-0522 “Bus Fail to Transfer”
- EK-0521 “2400V Standby Power Not Available” (85V secondary or 1700V primary)
- EK-0505 “2400V Bus 1E Bkr 152-302 Trip” (if closed)
- EK-0511 “2400V Bus 1E Bkr 152-303 Trip” (if closed)
2
Q
AOP-10 automatic actions
A
DEH Controller Power Supply switches to battery backup
3
Q
AOP-10 reactor trip criteria
A
Loss of Heater Drain Pump(s) results in Main Feedwater Pump(s) trip
4
Q
AOP-10 immediate actions
A
If loss of Heater Drain Pump(s) cause the Main Feedwater Pump(s) to trip, then trip the reactor