AOP-10 "Loss of Bus 1E" Flashcards

1
Q

AOP-10 entry conditions

A

Symptoms of loss of Bus 1E (loss of power to all Bus 1E powered components) in conjunction with 1 or more of the following:

  • EK-0517 “2400V Bus 1E Undervoltage” (90V secondary or 1860V primary)
  • EK-0522 “Bus Fail to Transfer”
  • EK-0521 “2400V Standby Power Not Available” (85V secondary or 1700V primary)
  • EK-0505 “2400V Bus 1E Bkr 152-302 Trip” (if closed)
  • EK-0511 “2400V Bus 1E Bkr 152-303 Trip” (if closed)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

AOP-10 automatic actions

A

DEH Controller Power Supply switches to battery backup

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

AOP-10 reactor trip criteria

A

Loss of Heater Drain Pump(s) results in Main Feedwater Pump(s) trip

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

AOP-10 immediate actions

A

If loss of Heater Drain Pump(s) cause the Main Feedwater Pump(s) to trip, then trip the reactor