AOP-35 "Loss of Service Water" Flashcards

1
Q

AOP-35 entry conditions

A
  • EK-1124 “Traveling Screen HI DP” (9” H2O)
  • EK-1129 “Service Water Pump Bay LO Level” (574’3”)
  • EK-1163 “Critical SW Header B LO Pressure” (45 psig)
  • EK-1164 “Critical SW Header A LO Pressure” (45 psig)
  • EK-1165 “Non-Critical SW Header LO Pressure” (45 psig)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

AOP-35 automatic actions

A
  • Standby SW Pump starts at 40 psig discharge pressure on an operating SW Pump
  • Screen Wash Pump P-4 starts at 6” H2O differential level across the Traveling Screens
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

AOP-35 reactor trip criteria

A
  • SW Bay Level <= 572’
  • Operator actions are not maintaining either Crit SW Header >= 42 psig
  • Loss of Non-Critical SW as indicated by the following alarms:
    • -EK-1165 “Non Critical SW LO Pressure” (45 psig)

AND

 --EK-0259 "Exciter Cooler High Temp" (50 C)

 OR

 --PPC Urgent Alarm "Exc Field Cold Air RTD-31" (48 C)

 OR

 --PPC Urgent Alarm "Exc Diode Cold Air RTD-32" (48 C)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

AOP-35 immediate actions

A

NOTE: EXCITER DAMAGE MAY OCCUR WITHIN 10 SECONDS OF LOSING NON-CRITICAL SERVICE WATER

Verify EK-1165 “Non Critical SW LO Press” is clear

  • If alarm is in and any of the following alarms are also in, then trip the reactor:
    • —-EK-0259 “Exciter Cooler HI Temp” (50 C)
    • —-PPC Urgent Alarm “Exc Field Cold Air RTD-31” (48 C)
    • —-PPC Urgent Alarm “Exc Diode Cold Air RTD-32” (48 C)
  • If alarm is in and any of the following occur, then perform Attachment 1 to break condenser vacuum:
    • —-Non-Critical SW has been lost or isolated
    • —-Exciter Cold Air Temperature > 80 C or rising